Molded Case Circuit Breakers (MCCB) NF-CS Series

Caution
- This product belongs in RoHS Directive under Category 9 "Monitoring and control equipment" with exclusion from the usage restriction of phthalate esters until 21 July 2021.
Product Description
Standard type small breaker.
[Features]
An economical product that is widely popular in the market.
· Width 67.5 mm (3P).
· Mountable on IEC 35 mm rail.
· Standard compliance to CE marking + CCC authentication (excludes NV).
· Earth leakage breaker handles higher harmonics and surges.
WS Series NF-C Type No-Fuse MITSUBISHI Circuit Breakers Specifications

Circuit Breakers Outline drawing
| Frame A | 30 | ||||
|---|---|---|---|---|---|
| Circuit Breakers Type Name | NF30-CS | ||||
| Rated Current A (Standard Ambient Temperature 40°C) | 3 5 10 15 20 30 | ||||
| Number of Poles | 2 | 3 | |||
| Rated Insulation Voltage V | 500 | ||||
| Rated Short Circuit Breakers Capacity kA | JIS C 8201-2-1 Ann.1 JIS C 8201-2-1 Ann.2 IEC 60947-2 EN 60947-2 (Icu/Ics) | AC | 690 V | - | |
| 500 V | - | ||||
| 440 V | - | ||||
| 415 V | 1.5/1.5 | ||||
| 400 V | 1.5/1.5 | ||||
| 380 V | 1.5/1.5 | ||||
| 240 V | 2.5/2 | ||||
| 200 V | 2.5/2 | ||||
| DC | 250 V | - | |||
| GB 14048.2 (Icu/Ics) | AC | 415 V | 1.5/1.5 | ||
| 400 V | 1.5/1.5 | ||||
| 380 V | 1.5/1.5 | ||||
| 240 V | 2.5/2 | ||||
| DC | 250 V | - | |||
| NK (Icu) | AC | 460 V | 1.5 | ||
| 250 V | 2.5 | ||||
| DC | 250 V | - | |||
| Rated Impulse Voltage Resistance Uimp (kV) | 4 | ||||
| Current Type | AC | ||||
| Isolation Compliant | - | ||||
| Reverse Connections | - | ||||
| Open And Closing Lifespan (Times) | Mechanical | 10,000 | |||
| Electrical | 6,000 (415 V AC) | ||||
| External Dimensions mm | a | 45 | 67.5 | ||
| b | 96 | ||||
| c | 52 | ||||
| ca | 67 | ||||
| Front Surface Type Product Mass kg | 0.25 | 0.35 | |||
| Connection Method | Front Surface Type (F) | ◎ For crimp terminals | |||
| Rear Surface Type (B) | △ Round studs (embedded) | ||||
| Accessory Devices Included | Alarm Switch (AL) | ○ (Note 1) | |||
| Auxiliary Switch (AX) | ○ (Note 1) | ||||
| Shunt Trip (SHT) | - | ||||
| Undervoltage Trip (UVT) | - | ||||
| Vertical Lead Terminal Block (SLT) | ○ | ||||
| Horizontal Lead Wire Terminal Block (LT) | - | ||||
| Parts Sold Separately | Circuit Breakers Box (In Box) | Enclosed Type (S) | ◎ | ||
| Dustproof Type (I) | - | ||||
| Waterproof Type (W) | - | ||||
| Handle Lock | LC | ◎ | |||
| HL | ◎ | ||||
| HL-S | - | ||||
| Operation Handle | F Type | - | |||
| V Type | - | ||||
| S Type | - | ||||
| C Type | - | ||||
| Terminal Cover (TC-L, TC-S, TTC, BTC) | ◎ | ||||
| Back Surface Stud (B-ST) | - | ||||
| IEC35 mm Rail Mounting Adapter | ◎ | ||||
| Electrical Appliance And Material Safety Law | compliant | ||||
| CE mark | TÜV certification | ||||
| CCC Certification | acquired | ||||
| Classification Society Certification (*Acquired) (NK, LR, ABS, GL) | *(NK, LR, ABS) | ||||
| Overcurrent Tripping Method | Completely electromagnetic | ||||
| Trip Button | -(Note 2) | ||||
(Circuit Breakers: Note 1) Lead wire routed out of the side is standard.
(Circuit Breakers: Note 2) Only included when an alarm switch (AL) is attached.
WS Series NF-C Type No-Fuse MITSUBISHI Circuit Breakers External Dimensions

Front Circuit Breakers Surface Type

Back Circuit Breakers Surface Type