NF63-CV Characteristics And External Shape of MITSUBISHI Circuit Breakers
| Type Name Circuit Breakers | NF63-CV Circuit Breakers | ||||
|---|---|---|---|---|---|
| Rated current In Standard ambient temperature 40°C (45°C for ships) A | 60 | ||||
| Number of contacts | 2 | 3 | |||
| Rated Insulation Voltage Ui V | 600 | ||||
| Rated short circuit breaking capacity kA | JIS C 8201-2-1 Ann. 1 JIS C 8201-2-1 Ann. 2 IEC 60947-2 EN 60947-2 (Icu/Ics) | AC | 690 V | - | |
| 500 V | 2.5/2.5 | ||||
| 440 V | 2.5/2.5 | ||||
| 415 V | 2.5/2.5 | ||||
| 400 V | 5/5 | ||||
| 380 V | 5/5 | ||||
| 230 V | 7.5/7.5 | ||||
| DC | 250 V (Note 1) | 2.5/2.5 | |||
| GB 14048.2 (Icu/Ics) | AC | 415 V | 2.5/2.5 | ||
| 400 V | 5/5 | ||||
| 380 V | 5/5 | ||||
| 230 V | 7.5/7.5 | ||||
| DC | 250 V | 2.5/2.5 | |||
| NK (Icu/Ics) | AC | 450 V | 2.5/2.5 | ||
| 240 V | 7.5/7.5 | ||||
| DC | 250 V | 2.5/2.5 | - | ||
Note 1: For 3-contact products, use two contacts.
NF63-CV Dimensional Outline Drawing of MITSUBISHI Circuit Breakers
Front Surface Type of MITSUBISHI Circuit Breakers

Back Surface Type of MITSUBISHI Circuit Breakers

Embedded Type of MITSUBISHI Circuit Breakers

Inserted Type of MITSUBISHI Circuit Breakers

NF125-CV Characteristics And External Shape of MITSUBISHI Circuit Breakers
| Type Name Circuit Breakers | NF125-CV Circuit Breakers | ||||||
|---|---|---|---|---|---|---|---|
| Rated current In Standard ambient temperature 40°C (45°C for ships) A | (50) 60 75 100 | 125 | |||||
| Number of contacts | 2 | 3 | 2 | 3 | |||
| Rated Insulation Voltage Ui V | 600 | 600 | |||||
| Rated short circuit breaking capacity kA | JIS C 8201-2-1Ann. 1 JIS C 8201-2-1Ann. 2 IEC 60947-2 EN 60947-2 (Icu/Ics) | AC | 690 V | - | - | ||
| 500 V | 7.5/4 | 7.5/4 | |||||
| 440 V | 10/5 | 10/5 | |||||
| 415 V | 10/5 | 10/5 | |||||
| 400 V | 10/5 | 10/5 | |||||
| 380 V | 10/5 | 10/5 | |||||
| 230 V | 30/15 | 30/15 | |||||
| DC | 250 V (Note 1) | 7.5/4 | 7.5/4 | ||||
| GB 14048.2 (Icu/Ics) | AC | 415 V | 10/5 | 10/5 | |||
| 400 V | 10/5 | 10/5 | |||||
| 380 V | 10/5 | 10/5 | |||||
| 230 V | 30/15 | 30/15 | |||||
| DC | 250 V | 7.5/4 | 7.5/4 | ||||
| NK (Icu/Ics) | AC | 450 V | 10/5 | 10/5 | |||
| 240 V | 30/15 | 30/15 | |||||
| DC | 250 V | 7.5/4 | - | 7.5/4 | - | ||
Note 1: For 3-contact products, use two contacts.
NF125-CV Dimensional Outline Drawing of MITSUBISHI Circuit Breakers
Front Surface Type of MITSUBISHI Circuit Breakers

Back Surface Type of MITSUBISHI Circuit Breakers

Embedded Type of MITSUBISHI Circuit Breakers

Note: NF125-CV for 2 and 3 contacts only, and motor breaker for 3 contacts only.
Inserted Type of MITSUBISHI Circuit Breakers