NF63-CV Single-Phase MCCB - 2/3 Contacts 60A

Caution
- This product belongs in RoHS Directive under Category 9 "Monitoring and control equipment" with exclusion from the usage restriction of phthalate esters until 21 July 2021.
Product Description
WS-V series NF-N type no-fuse breaker dedicated for single-phase 3 wire circuit.
[Features]
· Detects overvoltage above a specified level, and interrupts the circuit to protect load equipment.
· Connection method: front surface type, back surface type, embedded type.
[Applications]
· No-fuse breaker dedicated for single-phase 3-wire circuits.
Specification Table of MITSUBISHI Circuit Breakers NF63-CV
| Circuit Breakers Type Name | Circuit Breakers NF63-CV | ||||
|---|---|---|---|---|---|
| Rated current In Standard ambient temperature 40°C (45°C for ships) A | 60 | ||||
| Number of contacts | 2 | 3 | |||
| Rated Insulation Voltage Ui V | 600 | ||||
| Rated short circuit breaking capacity kA | JIS C 8201-2-1 Ann. 1 JIS C 8201-2-1 Ann. 2 IEC 60947-2 EN 60947-2 (Icu/Ics) | AC | 690 V | - | |
| 500 V | 2.5/2.5 | ||||
| 440 V | 2.5/2.5 | ||||
| 415 V | 2.5/2.5 | ||||
| 400 V | 5/5 | ||||
| 380 V | 5/5 | ||||
| 230 V | 7.5/7.5 | ||||
| DC | 250 V (Note 1) | 2.5/2.5 | |||
| GB 14048.2 (Icu/Ics) | AC | 415 V | 2.5/2.5 | ||
| 400 V | 5/5 | ||||
| 380 V | 5/5 | ||||
| 230 V | 7.5/7.5 | ||||
| DC | 250 V | 2.5/2.5 | |||
| NK (Icu/Ics) | AC | 450 V | 2.5/2.5 | ||
| 240 V | 7.5/7.5 | ||||
| DC | 250 V | 2.5/2.5 | - | ||
Note: For 13-contact products and 4-contact products, use 2 contacts.
Dimensional Drawing of MITSUBISHI Circuit Breakers NF63-CV
Front Surface Circuit Breakers Type

Back Surface Circuit Breakers Type

Embedded for Circuit Breakers Type

Inserted for Circuit Breakers Type

- Note: See the catalog for details on other Circuit Breakers products.