TeSys K Contactor

Brand :
Schneider Electric

Caution

    Product Description

    TeSys K contactor - 3P - AC-3 <= 440 V 6 A - 1 NC aux. - 24 V AC coil

    Product CodeProduct or component typeProduct certificationsSustainable offer statusEU RoHS DirectiveMercury freeRoHS exemption informationChina RoHS RegulationEnvironmental DisclosureCircularity ProfileWEEEOperating altitudeREACH RegulationREACH free of SVHCWarrantyUtilisation category[Uc] control circuit voltageRange[Ith] conventional free air thermal currentOvervoltage categoryPoles descriptionMaximum operating rateProtective treatmentProduct name                  Flame retardance                 Device application                      Irms rated making capacity                Contactor applicationPower pole contact compositionControl circuit type                   Rated breaking capacity                                    Associated fuse rating                    Average impedanceControl circuit voltage limitsOperating timeInrush power in VAHold-in power consumption in VAHeat dissipationMechanical robustness                        Safety reliability level                    Signalling circuit frequency                  Motor power kW                 Minimum switching currentAuxiliary contact compositionMinimum switching voltageInsulation resistance[Ie] rated operational currentAuxiliary contacts typeNon overlap distanceDevice short nameElectrical durabilityMechanical durabilityDepthIP degree of protectionStandardsAmbient air temperature for storageTightening torque[Ue] rated operational voltage[Ui] rated insulation voltageConnections - terminals[Uimp] rated impulse withstand voltageMounting supportHeightNet weight[Icw] rated short-time withstand currentWidth
    LC1K0601B7ContactorUL
    CSA
    Green Premium productCompliant  EU RoHS DeclarationYesYesChina RoHS declarationProduct Environmental ProfileEnd of Life InformationThe product must be disposed on European Union markets 
    following specific waste collection and never end up in rubbish bins
    2000 m without deratingREACH DeclarationYes18 monthsAC-4
    AC-3
    24 V AC 50/60 HzTeSys20 A (at 50 ℃) for power circuit
    10 A (at 50 ℃) for signalling circuit
    III3P3600 cyc/hTC conforming to IEC 60068
    TC conforming to DIN 50016
    TeSys KV1 conforming to UL 94
    Requirement 2 conforming to NF F 16-101
    Requirement 2 conforming to NF F 16-102
    Control110 A AC for power circuit conforming to NF C 63-110
    110 A AC for power circuit conforming to IEC 60947
    110 A AC for signalling circuit conforming to IEC 60947
    Motor control3 NOAC at 50/60 Hz110 A at 415 V conforming to IEC 60947
    110 A at 440 V conforming to IEC 60947
    80 A at 500 V conforming to IEC 60947
    110 A at 220...230 V conforming to IEC 60947
    110 A at 380...400 V conforming to IEC 60947
    70 A at 660...690 V conforming to IEC 60947
    25 A gG at <= 440 V for power circuit
    25 A aM for power circuit
    10 A gG for signalling circuit conforming to IEC 60947
    10 A gG for signalling circuit conforming to VDE 0660
    3 mOhm - Ith 20 A 50 Hz for power circuitOperational: 0.8...1.15 Uc (at <50 ℃)
    Drop-out: 0.2...0.75 Uc (at <50 ℃)
    10...20 ms coil de-energisation and NO opening
    10...20 ms coil energisation and NO closing
    30 VA (at 20 ℃)4.5 VA (at 20 ℃)1.3 WShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
    Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
    B10d = 1369863 cycles contactor 
    with nominal load conforming to EN/ISO 13849-1
    B10d = 20000000 cycles contactor 
    with mechanical load conforming to EN/ISO 13849-1
    <= 400 Hz1.5 kW at 220...230 V AC 50/60 Hz AC-3
    2.2 kW at 380...415 V AC 50/60 Hz AC-3
    3 kW at 440 V AC 50/60 Hz AC-3
    3 kW at 480 V AC 50/60 Hz AC-3
    3 kW at 500...600 V AC 50/60 Hz AC-3
    3 kW at 660...690 V AC 50/60 Hz AC-3
    1.5 kW at 400 V AC 50/60 Hz AC-4
    5 mA for signalling circuit1 NC17 V for signalling circuit> 10 MOhm for signalling circuit6 A at <= 440 V AC AC-3 for power circuitType instantaneous 1 NC0.5 mmLC1K1.3 Mcycles 6 A AC-3 at Ue <= 440 V10 Mcycles57 mmIP2x conforming to VDE 0106BS 5424
    IEC 60947
    NF C 63-110
    VDE 0660
    -50 to 80 ℃1.3 N.m - on screw clamp terminals - with screwdriver Philips No 2
    1.3 N.m - on screw clamp terminals - with screwdriver flat O 6 mm
    Power circuit: 690 V AC 50/60 Hz
    Signalling circuit: <= 690 V AC 50/60 Hz
    Power circuit: 600 V conforming to UL 508
    Power circuit: 690 V conforming to IEC 60947-4-1
    Signalling circuit: 690 V conforming to IEC 60947-4-1
    Signalling circuit: 690 V conforming to IEC 60947-5-1
    Signalling circuit: 600 V conforming to UL 508
    Power circuit: 600 V conforming to CSA C22.2 No 14
    Signalling circuit: 600 V conforming to CSA C22.2 No 14
    Screw clamp terminals 1 cable(s) 1.5 to 4 mm2solid
    Screw clamp terminals 1 cable(s) 0.75 to 4 mm2flexible without cable end
    Screw clamp terminals 1 cable(s) 0.34 to 2.5 mm2flexible with cable end
    Screw clamp terminals 2 cable(s) 1.5 to 4 mm2solid
    Screw clamp terminals 2 cable(s) 0.75 to 4 mm2flexible without cable end
    Screw clamp terminals 2 cable(s) 0.34 to 1.5 mm2flexible with cable end
    8 kVPlate
    Rail
    58 mm0.18 kg90 A 50 ℃ - 1 s for power circuit
    85 A 50 ℃ - 5 s for power circuit
    80 A 50 ℃ - 10 s for power circuit
    60 A 50 ℃ - 30 s for power circuit
    45 A 50 ℃ - 1 min for power circuit
    40 A 50 ℃ - 3 min for power circuit
    20 A 50 ℃ - >= 15 min for power circuit
    80 A - 1 s for signalling circuit
    90 A - 500 ms for signalling circuit
    110 A - 100 ms for signalling circuit
    45 mm
    LC1K0610B7ContactorUL
    CSA
    Green Premium productCompliant  EU RoHS DeclarationYesYesChina RoHS declarationProduct Environmental ProfileEnd of Life InformationThe product must be disposed on European Union markets 
    following specific waste collection and never end up in rubbish bins
    2000 m without deratingREACH DeclarationYes18 monthsAC-4
    AC-3
    24 V AC 50/60 HzTeSys20 A (at 50 ℃) for power circuit
    10 A (at 50 ℃) for signalling circuit
    III3P3600 cyc/hTC conforming to IEC 60068
    TC conforming to DIN 50016
    TeSys KV1 conforming to UL 94
    Requirement 2 conforming to NF F 16-101
    Requirement 2 conforming to NF F 16-102
    Control110 A AC for power circuit conforming to NF C 63-110
    110 A AC for power circuit conforming to IEC 60947
    110 A AC for signalling circuit conforming to IEC 60947
    Motor control3 NOAC at 50/60 Hz110 A at 415 V conforming to IEC 60947
    110 A at 440 V conforming to IEC 60947
    80 A at 500 V conforming to IEC 60947
    110 A at 220...230 V conforming to IEC 60947
    110 A at 380...400 V conforming to IEC 60947
    70 A at 660...690 V conforming to IEC 60947
    25 A gG at <= 440 V for power circuit
    25 A aM for power circuit
    10 A gG for signalling circuit conforming to IEC 60947
    10 A gG for signalling circuit conforming to VDE 0660
    3 mOhm - Ith 20 A 50 Hz for power circuitOperational: 0.8...1.15 Uc (at <50 ℃)
    Drop-out: 0.2...0.75 Uc (at <50 ℃)
    10...20 ms coil de-energisation and NO opening
    10...20 ms coil energisation and NO closing
    30 VA (at 20 ℃)4.5 VA (at 20 ℃)1.3 WShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
    Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
    B10d = 1369863 cycles contactor 
    with nominal load conforming to EN/ISO 13849-1
    B10d = 20000000 cycles contactor 
    with mechanical load conforming to EN/ISO 13849-1
    <= 400 Hz1.5 kW at 220...230 V AC 50/60 Hz AC-3
    2.2 kW at 380...415 V AC 50/60 Hz AC-3
    3 kW at 440 V AC 50/60 Hz AC-3
    3 kW at 480 V AC 50/60 Hz AC-3
    3 kW at 500...600 V AC 50/60 Hz AC-3
    3 kW at 660...690 V AC 50/60 Hz AC-3
    1.5 kW at 400 V AC 50/60 Hz AC-4
    5 mA for signalling circuit1 NO17 V for signalling circuit> 10 MOhm for signalling circuit6 A at <= 440 V AC AC-3 for power circuitType instantaneous 1 NO0.5 mmLC1K1.3 Mcycles 6 A AC-3 at Ue <= 440 V10 Mcycles57 mmIP2x conforming to VDE 0106BS 5424
    IEC 60947
    NF C 63-110
    VDE 0660
    -50 to 80 ℃1.3 N.m - on screw clamp terminals - with screwdriver Philips No 2
    1.3 N.m - on screw clamp terminals - with screwdriver flat O 6 mm
    Power circuit: 690 V AC 50/60 Hz
    Signalling circuit: <= 690 V AC 50/60 Hz
    Power circuit: 600 V conforming to UL 508
    Power circuit: 690 V conforming to IEC 60947-4-1
    Signalling circuit: 690 V conforming to IEC 60947-4-1
    Signalling circuit: 690 V conforming to IEC 60947-5-1
    Signalling circuit: 600 V conforming to UL 508
    Power circuit: 600 V conforming to CSA C22.2 No 14
    Signalling circuit: 600 V conforming to CSA C22.2 No 14
    Screw clamp terminals 1 cable(s) 1.5 to 4 mm2solid
    Screw clamp terminals 1 cable(s) 0.75 to 4 mm2flexible without cable end
    Screw clamp terminals 1 cable(s) 0.34 to 2.5 mm2flexible with cable end
    Screw clamp terminals 2 cable(s) 1.5 to 4 mm2solid
    Screw clamp terminals 2 cable(s) 0.75 to 4 mm2flexible without cable end
    Screw clamp terminals 2 cable(s) 0.34 to 1.5 mm2flexible with cable end
    8 kVRail
    Plate
    58 mm0.18 kg90 A 50 ℃ - 1 s for power circuit
    85 A 50 ℃ - 5 s for power circuit
    80 A 50 ℃ - 10 s for power circuit
    60 A 50 ℃ - 30 s for power circuit
    45 A 50 ℃ - 1 min for power circuit
    40 A 50 ℃ - 3 min for power circuit
    20 A 50 ℃ - >= 15 min for power circuit
    80 A - 1 s for signalling circuit
    90 A - 500 ms for signalling circuit
    110 A - 100 ms for signalling circuit
    45 mm
    LC1K0610E7ContactorCSA
    UL
    Green Premium productCompliant  EU RoHS DeclarationYesYesChina RoHS declarationProduct Environmental ProfileEnd of Life InformationThe product must be disposed on European Union markets 
    following specific waste collection and never end up in rubbish bins
    2000 m without deratingREACH DeclarationYes18 monthsAC-3
    AC-4
    48 V AC 50/60 HzTeSys20 A (at 50 ℃) for power circuit
    10 A (at 50 ℃) for signalling circuit
    III3P3600 cyc/hTC conforming to IEC 60068
    TC conforming to DIN 50016
    TeSys KV1 conforming to UL 94
    Requirement 2 conforming to NF F 16-101
    Requirement 2 conforming to NF F 16-102
    Control110 A AC for power circuit conforming to NF C 63-110
    110 A AC for power circuit conforming to IEC 60947
    110 A AC for signalling circuit conforming to IEC 60947
    Motor control3 NOAC at 50/60 Hz110 A at 415 V conforming to IEC 60947
    110 A at 440 V conforming to IEC 60947
    80 A at 500 V conforming to IEC 60947
    110 A at 220...230 V conforming to IEC 60947
    110 A at 380...400 V conforming to IEC 60947
    70 A at 660...690 V conforming to IEC 60947
    25 A gG at <= 440 V for power circuit
    25 A aM for power circuit
    10 A gG for signalling circuit conforming to IEC 60947
    10 A gG for signalling circuit conforming to VDE 0660
    3 mOhm - Ith 20 A 50 Hz for power circuitOperational: 0.8...1.15 Uc (at <50 ℃)
    Drop-out: 0.2...0.75 Uc (at <50 ℃)
    10...20 ms coil de-energisation and NO opening
    10...20 ms coil energisation and NO closing
    30 VA (at 20 ℃)4.5 VA (at 20 ℃)1.3 WShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
    Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
    B10d = 1369863 cycles contactor 
    with nominal load conforming to EN/ISO 13849-1
    B10d = 20000000 cycles contactor 
    with mechanical load conforming to EN/ISO 13849-1
    <= 400 Hz1.5 kW at 220...230 V AC 50/60 Hz AC-3
    2.2 kW at 380...415 V AC 50/60 Hz AC-3
    3 kW at 440 V AC 50/60 Hz AC-3
    3 kW at 480 V AC 50/60 Hz AC-3
    3 kW at 500...600 V AC 50/60 Hz AC-3
    3 kW at 660...690 V AC 50/60 Hz AC-3
    1.5 kW at 400 V AC 50/60 Hz AC-4
    5 mA for signalling circuit1 NO17 V for signalling circuit> 10 MOhm for signalling circuit6 A at <= 440 V AC AC-3 for power circuitType instantaneous 1 NO0.5 mmLC1K1.3 Mcycles 6 A AC-3 at Ue <= 440 V10 Mcycles57 mmIP2x conforming to VDE 0106BS 5424
    IEC 60947
    NF C 63-110
    VDE 0660
    -50 to 80 ℃1.3 N.m - on screw clamp terminals - with screwdriver Philips No 2
    1.3 N.m - on screw clamp terminals - with screwdriver flat O 6 mm
    Power circuit: 690 V AC 50/60 Hz
    Signalling circuit: <= 690 V AC 50/60 Hz
    Power circuit: 600 V conforming to UL 508
    Power circuit: 690 V conforming to IEC 60947-4-1
    Signalling circuit: 690 V conforming to IEC 60947-4-1
    Signalling circuit: 690 V conforming to IEC 60947-5-1
    Signalling circuit: 600 V conforming to UL 508
    Power circuit: 600 V conforming to CSA C22.2 No 14
    Signalling circuit: 600 V conforming to CSA C22.2 No 14
    Screw clamp terminals 1 cable(s) 1.5 to 4 mm2solid
    Screw clamp terminals 1 cable(s) 0.75 to 4 mm2flexible without cable end
    Screw clamp terminals 1 cable(s) 0.34 to 2.5 mm2flexible with cable end
    Screw clamp terminals 2 cable(s) 1.5 to 4 mm2solid
    Screw clamp terminals 2 cable(s) 0.75 to 4 mm2flexible without cable end
    Screw clamp terminals 2 cable(s) 0.34 to 1.5 mm2flexible with cable end
    8 kVRail
    Plate
    58 mm0.18 kg90 A 50 ℃ - 1 s for power circuit
    85 A 50 ℃ - 5 s for power circuit
    80 A 50 ℃ - 10 s for power circuit
    60 A 50 ℃ - 30 s for power circuit
    45 A 50 ℃ - 1 min for power circuit
    40 A 50 ℃ - 3 min for power circuit
    20 A 50 ℃ - >= 15 min for power circuit
    80 A - 1 s for signalling circuit
    90 A - 500 ms for signalling circuit
    110 A - 100 ms for signalling circuit
    45 mm
    LC1K0610M7ContactorUL
    CSA
    Green Premium productCompliant  EU RoHS DeclarationYesYesChina RoHS declarationProduct Environmental ProfileEnd of Life InformationThe product must be disposed on European Union markets 
    following specific waste collection and never end up in rubbish bins
    2000 m without deratingREACH DeclarationYes18 monthsAC-3
    AC-4
    220...230 V AC 50/60 HzTeSys20 A (at 50 ℃) for power circuit
    10 A (at 50 ℃) for signalling circuit
    III3P3600 cyc/hTC conforming to IEC 60068
    TC conforming to DIN 50016
    TeSys KV1 conforming to UL 94
    Requirement 2 conforming to NF F 16-101
    Requirement 2 conforming to NF F 16-102
    Control110 A AC for power circuit conforming to NF C 63-110
    110 A AC for power circuit conforming to IEC 60947
    110 A AC for signalling circuit conforming to IEC 60947
    Motor control3 NOAC at 50/60 Hz110 A at 415 V conforming to IEC 60947
    110 A at 440 V conforming to IEC 60947
    80 A at 500 V conforming to IEC 60947
    110 A at 220...230 V conforming to IEC 60947
    110 A at 380...400 V conforming to IEC 60947
    70 A at 660...690 V conforming to IEC 60947
    25 A gG at <= 440 V for power circuit
    25 A aM for power circuit
    10 A gG for signalling circuit conforming to IEC 60947
    10 A gG for signalling circuit conforming to VDE 0660
    3 mOhm - Ith 20 A 50 Hz for power circuitOperational: 0.8...1.15 Uc (at <50 ℃)
    Drop-out: 0.2...0.75 Uc (at <50 ℃)
    10...20 ms coil de-energisation and NO opening
    10...20 ms coil energisation and NO closing
    30 VA (at 20 ℃)4.5 VA (at 20 ℃)1.3 WShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
    Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
    B10d = 1369863 cycles contactor 
    with nominal load conforming to EN/ISO 13849-1
    B10d = 20000000 cycles contactor 
    with mechanical load conforming to EN/ISO 13849-1
    <= 400 Hz1.5 kW at 220...230 V AC 50/60 Hz AC-3
    2.2 kW at 380...415 V AC 50/60 Hz AC-3
    3 kW at 440 V AC 50/60 Hz AC-3
    3 kW at 480 V AC 50/60 Hz AC-3
    3 kW at 500...600 V AC 50/60 Hz AC-3
    3 kW at 660...690 V AC 50/60 Hz AC-3
    1.5 kW at 400 V AC 50/60 Hz AC-4
    5 mA for signalling circuit1 NO17 V for signalling circuit> 10 MOhm for signalling circuit6 A at <= 440 V AC AC-3 for power circuitType instantaneous 1 NO0.5 mmLC1K1.3 Mcycles 6 A AC-3 at Ue <= 440 V10 Mcycles57 mmIP2x conforming to VDE 0106BS 5424
    IEC 60947
    NF C 63-110
    VDE 0660
    -50 to 80 ℃1.3 N.m - on screw clamp terminals - with screwdriver Philips No 2
    1.3 N.m - on screw clamp terminals - with screwdriver flat O 6 mm
    Power circuit: 690 V AC 50/60 Hz
    Signalling circuit: <= 690 V AC 50/60 Hz
    Power circuit: 600 V conforming to UL 508
    Power circuit: 690 V conforming to IEC 60947-4-1
    Signalling circuit: 690 V conforming to IEC 60947-4-1
    Signalling circuit: 690 V conforming to IEC 60947-5-1
    Signalling circuit: 600 V conforming to UL 508
    Power circuit: 600 V conforming to CSA C22.2 No 14
    Signalling circuit: 600 V conforming to CSA C22.2 No 14
    Screw clamp terminals 1 cable(s) 1.5 to 4 mm2solid
    Screw clamp terminals 1 cable(s) 0.75 to 4 mm2flexible without cable end
    Screw clamp terminals 1 cable(s) 0.34 to 2.5 mm2flexible with cable end
    Screw clamp terminals 2 cable(s) 1.5 to 4 mm2solid
    Screw clamp terminals 2 cable(s) 0.75 to 4 mm2flexible without cable end
    Screw clamp terminals 2 cable(s) 0.34 to 1.5 mm2flexible with cable end
    8 kVRail
    Plate
    58 mm0.18 kg90 A 50 ℃ - 1 s for power circuit
    85 A 50 ℃ - 5 s for power circuit
    80 A 50 ℃ - 10 s for power circuit
    60 A 50 ℃ - 30 s for power circuit
    45 A 50 ℃ - 1 min for power circuit
    40 A 50 ℃ - 3 min for power circuit
    20 A 50 ℃ - >= 15 min for power circuit
    80 A - 1 s for signalling circuit
    90 A - 500 ms for signalling circuit
    110 A - 100 ms for signalling circuit
    45 mm
    LC1K09008M7ContactorUL
    CSA
    Green Premium productCompliant  EU RoHS DeclarationYesYesChina RoHS declarationProduct Environmental ProfileEnd of Life InformationThe product must be disposed on European Union markets 
    following specific waste collection and never end up in rubbish bins
    2000 m without deratingREACH DeclarationYes18 monthsAC-1220...230 V AC 50/60 HzTeSys20 A (at 50 ℃) for power circuitIII4P3600 cyc/hTC conforming to IEC 60068
    TC conforming to DIN 50016
    TeSys KV1 conforming to UL 94
    Requirement 2 conforming to NF F 16-101
    Requirement 2 conforming to NF F 16-102
    Control110 A AC for power circuit conforming to NF C 63-110
    110 A AC for power circuit conforming to IEC 60947
    Resistive load2 NO + 2 NCAC at 50/60 Hz110 A at 415 V conforming to IEC 60947
    110 A at 440 V conforming to IEC 60947
    80 A at 500 V conforming to IEC 60947
    110 A at 220...230 V conforming to IEC 60947
    110 A at 380...400 V conforming to IEC 60947
    70 A at 660...690 V conforming to IEC 60947
    25 A gG at <= 440 V for power circuit
    25 A aM for power circuit
    3 mOhm - Ith 20 A 50 Hz for power circuitOperational: 0.8...1.15 Uc (at <50 ℃)
    Drop-out: 0.2...0.75 Uc (at <50 ℃)
    10...20 ms coil de-energisation and NO opening
    10...20 ms coil energisation and NO closing
    15...25 ms coil de-energisation and NC closing
    5...15 ms coil energisation and NC opening
    30 VA (at 20 ℃)4.5 VA (at 20 ℃)1.3 WShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
    Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
    B10d = 1369863 cycles contactor 
    with nominal load conforming to EN/ISO 13849-1
    B10d = 20000000 cycles contactor 
    with mechanical load conforming to EN/ISO 13849-1
    <= 400 Hz---------0.18 Mcycles 20 A AC-1 at Ue <= 440 V10 Mcycles57 mmIP2x conforming to VDE 0106BS 5424
    IEC 60947
    NF C 63-110
    VDE 0660
    -50 to 80 ℃1.3 N.m - on screw clamp terminals - with screwdriver Philips No 2
    1.3 N.m - on screw clamp terminals - with screwdriver flat O 6 mm
    Power circuit: 690 V AC 50/60 HzPower circuit: 600 V conforming to UL 508
    Power circuit: 690 V conforming to IEC 60947-4-1
    Power circuit: 600 V conforming to CSA C22.2 No 14
    Screw clamp terminals 1 cable(s) 1.5 to 4 mm2solid
    Screw clamp terminals 1 cable(s) 0.75 to 4 mm2flexible without cable end
    Screw clamp terminals 1 cable(s) 0.34 to 2.5 mm2flexible with cable end
    Screw clamp terminals 2 cable(s) 1.5 to 4 mm2solid
    Screw clamp terminals 2 cable(s) 0.75 to 4 mm2flexible without cable end
    Screw clamp terminals 2 cable(s) 0.34 to 1.5 mm2flexible with cable end
    8 kVPlate
    Rail
    ----
    LC1K0901B7ContactorCSA
    UL
    Green Premium productCompliant  EU RoHS DeclarationYesYesChina RoHS declarationProduct Environmental ProfileEnd of Life InformationThe product must be disposed on European Union markets 
    following specific waste collection and never end up in rubbish bins
    2000 m without deratingREACH DeclarationYes18 monthsAC-3
    AC-4
    AC-1
    24 V AC 50/60 HzTeSys20 A (at 50 ℃) for power circuit
    10 A (at 50 ℃) for signalling circuit
    III3P3600 cyc/hTC conforming to IEC 60068
    TC conforming to DIN 50016
    TeSys KV1 conforming to UL 94
    Requirement 2 conforming to NF F 16-101
    Requirement 2 conforming to NF F 16-102
    Control110 A AC for power circuit conforming to NF C 63-110
    110 A AC for power circuit conforming to IEC 60947
    110 A AC for signalling circuit conforming to IEC 60947
    Resistive load
    Motor control
    3 NOAC at 50/60 Hz110 A at 415 V conforming to IEC 60947
    110 A at 440 V conforming to IEC 60947
    80 A at 500 V conforming to IEC 60947
    110 A at 220...230 V conforming to IEC 60947
    110 A at 380...400 V conforming to IEC 60947
    70 A at 660...690 V conforming to IEC 60947
    25 A gG at <= 440 V for power circuit
    25 A aM for power circuit
    10 A gG for signalling circuit conforming to IEC 60947
    10 A gG for signalling circuit conforming to VDE 0660
    3 mOhm - Ith 20 A 50 Hz for power circuitOperational: 0.8...1.15 Uc (at <50 ℃)
    Drop-out: 0.2...0.75 Uc (at <50 ℃)
    10...20 ms coil de-energisation and NO opening
    10...20 ms coil energisation and NO closing
    30 VA (at 20 ℃)4.5 VA (at 20 ℃)1.3 WShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
    Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
    B10d = 1369863 cycles contactor 
    with nominal load conforming to EN/ISO 13849-1
    B10d = 20000000 cycles contactor 
    with mechanical load conforming to EN/ISO 13849-1
    <= 400 Hz2.2 kW at 220...230 V AC 50/60 Hz AC-3
    4 kW at 380...415 V AC 50/60 Hz AC-3
    4 kW at 440 V AC 50/60 Hz AC-3
    4 kW at 480 V AC 50/60 Hz AC-3
    4 kW at 500...600 V AC 50/60 Hz AC-3
    4 kW at 660...690 V AC 50/60 Hz AC-3
    2.2 kW at 400 V AC 50/60 Hz AC-4
    5 mA for signalling circuit1 NC17 V for signalling circuit> 10 MOhm for signalling circuit20 A (at <50 ℃) at <= 440 V AC AC-1 for power circuit
    9 A at <= 440 V AC AC-3 for power circuit
    16 A (at <70 ℃) at 690 V AC AC-1 for power circuit
    Type instantaneous 1 NC0.5 mmLC1K0.18 Mcycles 20 A AC-1 at Ue <= 440 V
    1.3 Mcycles 9 A AC-3 at Ue <= 440 V
    10 Mcycles57 mmIP2x conforming to VDE 0106BS 5424
    IEC 60947
    NF C 63-110
    VDE 0660
    -50 to 80 ℃1.3 N.m - on screw clamp terminals - with screwdriver Philips No 2
    1.3 N.m - on screw clamp terminals - with screwdriver flat O 6 mm
    Power circuit: 690 V AC 50/60 Hz
    Signalling circuit: <= 690 V AC 50/60 Hz
    Power circuit: 600 V conforming to UL 508
    Power circuit: 690 V conforming to IEC 60947-4-1
    Signalling circuit: 690 V conforming to IEC 60947-4-1
    Signalling circuit: 690 V conforming to IEC 60947-5-1
    Signalling circuit: 600 V conforming to UL 508
    Power circuit: 600 V conforming to CSA C22.2 No 14
    Signalling circuit: 600 V conforming to CSA C22.2 No 14
    Screw clamp terminals 1 cable(s) 1.5 to 4 mm2solid
    Screw clamp terminals 1 cable(s) 0.75 to 4 mm2flexible without cable end
    Screw clamp terminals 1 cable(s) 0.34 to 2.5 mm2flexible with cable end
    Screw clamp terminals 2 cable(s) 1.5 to 4 mm2solid
    Screw clamp terminals 2 cable(s) 0.75 to 4 mm2flexible without cable end
    Screw clamp terminals 2 cable(s) 0.34 to 1.5 mm2flexible with cable end
    8 kVPlate
    Rail
    58 mm0.18 kg90 A 50 ℃ - 1 s for power circuit
    85 A 50 ℃ - 5 s for power circuit
    80 A 50 ℃ - 10 s for power circuit
    60 A 50 ℃ - 30 s for power circuit
    45 A 50 ℃ - 1 min for power circuit
    40 A 50 ℃ - 3 min for power circuit
    20 A 50 ℃ - >= 15 min for power circuit
    80 A - 1 s for signalling circuit
    90 A - 500 ms for signalling circuit
    110 A - 100 ms for signalling circuit
    -
    LC1K0910B7ContactorCSA
    UL
    Green Premium productCompliant  EU RoHS DeclarationYesYesChina RoHS declarationProduct Environmental ProfileEnd of Life InformationThe product must be disposed on European Union markets 
    following specific waste collection and never end up in rubbish bins
    2000 m without deratingREACH DeclarationYes18 monthsAC-3
    AC-1
    AC-4
    24 V AC 50/60 HzTeSys20 A (at 50 ℃) for power circuit
    10 A (at 50 ℃) for signalling circuit
    III3P3600 cyc/hTC conforming to IEC 60068
    TC conforming to DIN 50016
    TeSys KV1 conforming to UL 94
    Requirement 2 conforming to NF F 16-101
    Requirement 2 conforming to NF F 16-102
    Control110 A AC for power circuit conforming to NF C 63-110
    110 A AC for power circuit conforming to IEC 60947
    110 A AC for signalling circuit conforming to IEC 60947
    Motor control
    Resistive load
    3 NOAC at 50/60 Hz110 A at 415 V conforming to IEC 60947
    110 A at 440 V conforming to IEC 60947
    80 A at 500 V conforming to IEC 60947
    110 A at 220...230 V conforming to IEC 60947
    110 A at 380...400 V conforming to IEC 60947
    70 A at 660...690 V conforming to IEC 60947
    25 A gG at <= 440 V for power circuit
    25 A aM for power circuit
    10 A gG for signalling circuit conforming to IEC 60947
    10 A gG for signalling circuit conforming to VDE 0660
    3 mOhm - Ith 20 A 50 Hz for power circuitOperational: 0.8...1.15 Uc (at <50 ℃)
    Drop-out: 0.2...0.75 Uc (at <50 ℃)
    10...20 ms coil de-energisation and NO opening
    10...20 ms coil energisation and NO closing
    30 VA (at 20 ℃)4.5 VA (at 20 ℃)1.3 WShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
    Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
    B10d = 1369863 cycles contactor 
    with nominal load conforming to EN/ISO 13849-1
    B10d = 20000000 cycles contactor 
    with mechanical load conforming to EN/ISO 13849-1
    <= 400 Hz2.2 kW at 220...230 V AC 50/60 Hz AC-3
    4 kW at 380...415 V AC 50/60 Hz AC-3
    4 kW at 440 V AC 50/60 Hz AC-3
    4 kW at 480 V AC 50/60 Hz AC-3
    4 kW at 500...600 V AC 50/60 Hz AC-3
    4 kW at 660...690 V AC 50/60 Hz AC-3
    2.2 kW at 400 V AC 50/60 Hz AC-4
    5 mA for signalling circuit1 NO17 V for signalling circuit> 10 MOhm for signalling circuit20 A (at <50 ℃) at <= 440 V AC AC-1 for power circuit
    9 A at <= 440 V AC AC-3 for power circuit
    16 A (at <70 ℃) at 690 V AC AC-1 for power circuit
    Type instantaneous 1 NO0.5 mmLC1K----------------
    LC1K0910E7ContactorUL
    CSA
    Green Premium productCompliant  EU RoHS DeclarationYesYesChina RoHS declarationProduct Environmental ProfileEnd of Life InformationThe product must be disposed on European Union markets 
    following specific waste collection and never end up in rubbish bins
    2000 m without deratingREACH DeclarationYes18 monthsAC-1
    AC-3
    AC-4
    48 V AC 50/60 HzTeSys20 A (at 50 ℃) for power circuit
    10 A (at 50 ℃) for signalling circuit
    III3P3600 cyc/hTC conforming to IEC 60068
    TC conforming to DIN 50016
    TeSys KV1 conforming to UL 94
    Requirement 2 conforming to NF F 16-101
    Requirement 2 conforming to NF F 16-102
    Control110 A AC for power circuit conforming to NF C 63-110
    110 A AC for power circuit conforming to IEC 60947
    110 A AC for signalling circuit conforming to IEC 60947
    Resistive load
    Motor control
    3 NOAC at 50/60 Hz110 A at 415 V conforming to IEC 60947
    110 A at 440 V conforming to IEC 60947
    80 A at 500 V conforming to IEC 60947
    110 A at 220...230 V conforming to IEC 60947
    110 A at 380...400 V conforming to IEC 60947
    70 A at 660...690 V conforming to IEC 60947
    25 A gG at <= 440 V for power circuit
    25 A aM for power circuit
    10 A gG for signalling circuit conforming to IEC 60947
    10 A gG for signalling circuit conforming to VDE 0660
    3 mOhm - Ith 20 A 50 Hz for power circuitOperational: 0.8...1.15 Uc (at <50 ℃)
    Drop-out: 0.2...0.75 Uc (at <50 ℃)
    10...20 ms coil de-energisation and NO opening
    10...20 ms coil energisation and NO closing
    30 VA (at 20 ℃)4.5 VA (at 20 ℃)1.3 WShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
    Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
    B10d = 1369863 cycles contactor 
    with nominal load conforming to EN/ISO 13849-1
    B10d = 20000000 cycles contactor 
    with mechanical load conforming to EN/ISO 13849-1
    <= 400 Hz2.2 kW at 220...230 V AC 50/60 Hz AC-3
    4 kW at 380...415 V AC 50/60 Hz AC-3
    4 kW at 440 V AC 50/60 Hz AC-3
    4 kW at 480 V AC 50/60 Hz AC-3
    4 kW at 500...600 V AC 50/60 Hz AC-3
    4 kW at 660...690 V AC 50/60 Hz AC-3
    2.2 kW at 400 V AC 50/60 Hz AC-4
    5 mA for signalling circuit1 NO17 V for signalling circuit> 10 MOhm for signalling circuit20 A (at <50 ℃) at <= 440 V AC AC-1 for power circuit
    9 A at <= 440 V AC AC-3 for power circuit
    16 A (at <70 ℃) at 690 V AC AC-1 for power circuit
    Type instantaneous 1 NO0.5 mmLC1K----------------
    LC1K0910G7ContactorUL
    CSA
    Green Premium productCompliant  EU RoHS DeclarationYesYesChina RoHS declarationProduct Environmental ProfileEnd of Life InformationThe product must be disposed on European Union markets 
    following specific waste collection and never end up in rubbish bins
    2000 m without deratingREACH DeclarationYes18 monthsAC-1
    AC-3
    AC-4
    120 V AC 50/60 HzTeSys20 A (at 50 ℃) for power circuit
    10 A (at 50 ℃) for signalling circuit
    III3P3600 cyc/hTC conforming to IEC 60068
    TC conforming to DIN 50016
    TeSys KV1 conforming to UL 94
    Requirement 2 conforming to NF F 16-101
    Requirement 2 conforming to NF F 16-102
    Control110 A AC for power circuit conforming to NF C 63-110
    110 A AC for power circuit conforming to IEC 60947
    110 A AC for signalling circuit conforming to IEC 60947
    Motor control
    Resistive load
    3 NOAC at 50/60 Hz110 A at 415 V conforming to IEC 60947
    110 A at 440 V conforming to IEC 60947
    80 A at 500 V conforming to IEC 60947
    110 A at 220...230 V conforming to IEC 60947
    110 A at 380...400 V conforming to IEC 60947
    70 A at 660...690 V conforming to IEC 60947
    25 A gG at <= 440 V for power circuit
    25 A aM for power circuit
    10 A gG for signalling circuit conforming to IEC 60947
    10 A gG for signalling circuit conforming to VDE 0660
    3 mOhm - Ith 20 A 50 Hz for power circuitOperational: 0.8...1.15 Uc (at <50 ℃)
    Drop-out: 0.2...0.75 Uc (at <50 ℃)
    10...20 ms coil de-energisation and NO opening
    10...20 ms coil energisation and NO closing
    30 VA (at 20 ℃)4.5 VA (at 20 ℃)1.3 WShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
    Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
    B10d = 1369863 cycles contactor 
    with nominal load conforming to EN/ISO 13849-1
    B10d = 20000000 cycles contactor 
    with mechanical load conforming to EN/ISO 13849-1
    <= 400 Hz2.2 kW at 220...230 V AC 50/60 Hz AC-3
    4 kW at 380...415 V AC 50/60 Hz AC-3
    4 kW at 440 V AC 50/60 Hz AC-3
    4 kW at 480 V AC 50/60 Hz AC-3
    4 kW at 500...600 V AC 50/60 Hz AC-3
    4 kW at 660...690 V AC 50/60 Hz AC-3
    2.2 kW at 400 V AC 50/60 Hz AC-4
    5 mA for signalling circuit1 NO17 V for signalling circuit> 10 MOhm for signalling circuit20 A (at <50 ℃) at <= 440 V AC AC-1 for power circuit
    9 A at <= 440 V AC AC-3 for power circuit
    16 A (at <70 ℃) at 690 V AC AC-1 for power circuit
    Type instantaneous 1 NO0.5 mmLC1K----------------
    LC1K0910M7ContactorCSA
    UL
    Green Premium productCompliant  EU RoHS DeclarationYesYesChina RoHS declarationProduct Environmental ProfileEnd of Life InformationThe product must be disposed on European Union markets 
    following specific waste collection and never end up in rubbish bins
    2000 m without deratingREACH DeclarationYes18 monthsAC-4
    AC-3
    AC-1
    220...230 V AC 50/60 HzTeSys20 A (at 50 ℃) for power circuit
    10 A (at 50 ℃) for signalling circuit
    III3P3600 cyc/hTC conforming to IEC 60068
    TC conforming to DIN 50016
    TeSys KV1 conforming to UL 94
    Requirement 2 conforming to NF F 16-101
    Requirement 2 conforming to NF F 16-102
    Control110 A AC for power circuit conforming to NF C 63-110
    110 A AC for power circuit conforming to IEC 60947
    110 A AC for signalling circuit conforming to IEC 60947
    Motor control
    Resistive load
    3 NOAC at 50/60 Hz110 A at 415 V conforming to IEC 60947
    110 A at 440 V conforming to IEC 60947
    80 A at 500 V conforming to IEC 60947
    110 A at 220...230 V conforming to IEC 60947
    110 A at 380...400 V conforming to IEC 60947
    70 A at 660...690 V conforming to IEC 60947
    25 A gG at <= 440 V for power circuit
    25 A aM for power circuit
    10 A gG for signalling circuit conforming to IEC 60947
    10 A gG for signalling circuit conforming to VDE 0660
    3 mOhm - Ith 20 A 50 Hz for power circuitOperational: 0.8...1.15 Uc (at <50 ℃)
    Drop-out: 0.2...0.75 Uc (at <50 ℃)
    10...20 ms coil de-energisation and NO opening
    10...20 ms coil energisation and NO closing
    30 VA (at 20 ℃)4.5 VA (at 20 ℃)1.3 WShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
    Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
    B10d = 1369863 cycles contactor 
    with nominal load conforming to EN/ISO 13849-1
    B10d = 20000000 cycles contactor 
    with mechanical load conforming to EN/ISO 13849-1
    <= 400 Hz2.2 kW at 220...230 V AC 50/60 Hz AC-3
    4 kW at 380...415 V AC 50/60 Hz AC-3
    4 kW at 440 V AC 50/60 Hz AC-3
    4 kW at 480 V AC 50/60 Hz AC-3
    4 kW at 500...600 V AC 50/60 Hz AC-3
    4 kW at 660...690 V AC 50/60 Hz AC-3
    2.2 kW at 400 V AC 50/60 Hz AC-4
    5 mA for signalling circuit1 NO17 V for signalling circuit> 10 MOhm for signalling circuit20 A (at <50 ℃) at <= 440 V AC AC-1 for power circuit
    9 A at <= 440 V AC AC-3 for power circuit
    16 A (at <70 ℃) at 690 V AC AC-1 for power circuit
    Type instantaneous 1 NO0.5 mm-----------------
    LC1K1201E7ContactorCSA
    UL
    Green Premium productCompliant  EU RoHS DeclarationYesYesChina RoHS declarationProduct Environmental ProfileEnd of Life InformationThe product must be disposed on European Union markets 
    following specific waste collection and never end up in rubbish bins
    2000 m without deratingREACH DeclarationYes18 monthsAC-3
    AC-4
    AC-1
    48 V AC 50/60 HzTeSys20 A (at 50 ℃) for power circuit
    10 A (at 50 ℃) for signalling circuit
    III3P3600 cyc/hTC conforming to IEC 60068
    TC conforming to DIN 50016
    TeSys KV1 conforming to UL 94
    Requirement 2 conforming to NF F 16-101
    Requirement 2 conforming to NF F 16-102
    Control110 A AC for signalling circuit conforming to IEC 60947
    144 A AC for power circuit conforming to NF C 63-110
    144 A AC for power circuit conforming to IEC 60947
    Motor control
    Resistive load
    3 NOAC at 50/60 Hz110 A at 440 V conforming to IEC 60947
    80 A at 500 V conforming to IEC 60947
    70 A at 660...690 V conforming to IEC 60947
    25 A gG at <= 440 V for power circuit
    25 A aM for power circuit
    10 A gG for signalling circuit conforming to IEC 60947
    10 A gG for signalling circuit conforming to VDE 0660
    3 mOhm - Ith 20 A 50 Hz for power circuitOperational: 0.8...1.15 Uc (at <50 ℃)
    Drop-out: 0.2...0.75 Uc (at <50 ℃)
    10...20 ms coil de-energisation and NO opening
    10...20 ms coil energisation and NO closing
    30 VA (at 20 ℃)4.5 VA (at 20 ℃)1.3 WShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
    Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
    B10d = 1369863 cycles contactor 
    with nominal load conforming to EN/ISO 13849-1
    B10d = 20000000 cycles contactor 
    with mechanical load conforming to EN/ISO 13849-1
    <= 400 Hz4 kW at 480 V AC 50/60 Hz AC-3
    4 kW at 500...600 V AC 50/60 Hz AC-3
    4 kW at 660...690 V AC 50/60 Hz AC-3
    2.2 kW at 400 V AC 50/60 Hz AC-4
    3 kW at 220...230 V AC 50/60 Hz AC-3
    5.5 kW at 380...415 V AC 50/60 Hz AC-3
    5.5 kW at 440 V AC 50/60 Hz AC-3
    5 mA for signalling circuit1 NC17 V for signalling circuit> 10 MOhm for signalling circuit20 A (at <50 ℃) at <= 440 V AC AC-1 for power circuit
    12 A at <= 440 V AC AC-3 for power circuit
    16 A (at <70 ℃) at 690 V AC AC-1 for power circuit
    Type instantaneous 1 NC0.5 mmLC1K----------------
    LC1K1201F7ContactorUL
    CSA
    Green Premium productCompliant  EU RoHS DeclarationYesYesChina RoHS declarationProduct Environmental ProfileEnd of Life InformationThe product must be disposed on European Union markets 
    following specific waste collection and never end up in rubbish bins
    2000 m without deratingREACH DeclarationYes18 monthsAC-4
    AC-1
    AC-3
    110 V AC 50/60 HzTeSys20 A (at 50 ℃) for power circuit
    10 A (at 50 ℃) for signalling circuit
    III3P3600 cyc/hTC conforming to IEC 60068
    TC conforming to DIN 50016
    TeSys KV1 conforming to UL 94
    Requirement 2 conforming to NF F 16-101
    Requirement 2 conforming to NF F 16-102
    Control110 A AC for signalling circuit conforming to IEC 60947
    144 A AC for power circuit conforming to NF C 63-110
    144 A AC for power circuit conforming to IEC 60947
    Resistive load
    Motor control
    3 NOAC at 50/60 Hz110 A at 440 V conforming to IEC 60947
    80 A at 500 V conforming to IEC 60947
    70 A at 660...690 V conforming to IEC 60947
    25 A gG at <= 440 V for power circuit
    25 A aM for power circuit
    10 A gG for signalling circuit conforming to IEC 60947
    10 A gG for signalling circuit conforming to VDE 0660
    3 mOhm - Ith 20 A 50 Hz for power circuitOperational: 0.8...1.15 Uc (at <50 ℃)
    Drop-out: 0.2...0.75 Uc (at <50 ℃)
    10...20 ms coil de-energisation and NO opening
    10...20 ms coil energisation and NO closing
    30 VA (at 20 ℃)4.5 VA (at 20 ℃)1.3 WShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
    Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
    B10d = 1369863 cycles contactor 
    with nominal load conforming to EN/ISO 13849-1
    B10d = 20000000 cycles contactor 
    with mechanical load conforming to EN/ISO 13849-1
    <= 400 Hz4 kW at 480 V AC 50/60 Hz AC-3
    4 kW at 500...600 V AC 50/60 Hz AC-3
    4 kW at 660...690 V AC 50/60 Hz AC-3
    2.2 kW at 400 V AC 50/60 Hz AC-4
    3 kW at 220...230 V AC 50/60 Hz AC-3
    5.5 kW at 380...415 V AC 50/60 Hz AC-3
    5.5 kW at 440 V AC 50/60 Hz AC-3
    5 mA for signalling circuit1 NC17 V for signalling circuit> 10 MOhm for signalling circuit20 A (at <50 ℃) at <= 440 V AC AC-1 for power circuit
    12 A at <= 440 V AC AC-3 for power circuit
    16 A (at <70 ℃) at 690 V AC AC-1 for power circuit
    Type instantaneous 1 NC0.5 mmLC1K----------------
    Viewed Products
    Recently Viewed Products
    My Components
    My Components
    0
    Cart
    Cart
    Economy Series
    MRO Product

    Chat with MISUMI

    Chat service is available for any inquiry to MISUMI

    Service hours

    9:00 - 18:00 (Mon-Sat)

    For out of service hours, you can leave a message to us.
    We will reply to your inquiries on the next business day.
    (except Sundays and public holidays).

    Noted for use

    Chat service is for Corporate customers and limited for Thai language.

    Request for Quotation and Place Order is not available on Chat.

    Start chat