WS-V series NF-C type no-fuse breaker (economy product).
[Features]
· Small, high performance, and economical no-fuse breaker.
· Smallest breaker in the industry.
· Connection method: front surface type, back surface type, embedded type, inserted type.
[Applications]
· No-fuse breaker, economy product.
Type Name | NF63-CV | ||||
---|---|---|---|---|---|
Rated current In Standard ambient temperature 40°C (45°C for ships) A | 60 | ||||
Number of contacts | 2 | 3 | |||
Rated Insulation Voltage Ui V | 600 | ||||
Rated short circuit breaking capacity kA | JIS C 8201-2-1 Ann. 1 JIS C 8201-2-1 Ann. 2 IEC 60947-2 EN 60947-2 (Icu/Ics) | AC | 690 V | - | |
500 V | 2.5/2.5 | ||||
440 V | 2.5/2.5 | ||||
415 V | 2.5/2.5 | ||||
400 V | 5/5 | ||||
380 V | 5/5 | ||||
230 V | 7.5/7.5 | ||||
DC | 250 V (Note 1) | 2.5/2.5 | |||
GB 14048.2 (Icu/Ics) | AC | 415 V | 2.5/2.5 | ||
400 V | 5/5 | ||||
380 V | 5/5 | ||||
230 V | 7.5/7.5 | ||||
DC | 250 V | 2.5/2.5 | |||
NK (Icu/Ics) | AC | 450 V | 2.5/2.5 | ||
240 V | 7.5/7.5 | ||||
DC | 250 V | 2.5/2.5 | - |
Note 1: For 3-contact products, use two contacts.
Type Name | NF125-CV | ||||||
---|---|---|---|---|---|---|---|
Rated current In Standard ambient temperature 40°C (45°C for ships) A | (50) 60 75 100 | 125 | |||||
Number of contacts | 2 | 3 | 2 | 3 | |||
Rated Insulation Voltage Ui V | 600 | 600 | |||||
Rated short circuit breaking capacity kA | JIS C 8201-2-1Ann. 1 JIS C 8201-2-1Ann. 2 IEC 60947-2 EN 60947-2 (Icu/Ics) | AC | 690 V | - | - | ||
500 V | 7.5/4 | 7.5/4 | |||||
440 V | 10/5 | 10/5 | |||||
415 V | 10/5 | 10/5 | |||||
400 V | 10/5 | 10/5 | |||||
380 V | 10/5 | 10/5 | |||||
230 V | 30/15 | 30/15 | |||||
DC | 250 V (Note 1) | 7.5/4 | 7.5/4 | ||||
GB 14048.2 (Icu/Ics) | AC | 415 V | 10/5 | 10/5 | |||
400 V | 10/5 | 10/5 | |||||
380 V | 10/5 | 10/5 | |||||
230 V | 30/15 | 30/15 | |||||
DC | 250 V | 7.5/4 | 7.5/4 | ||||
NK (Icu/Ics) | AC | 450 V | 10/5 | 10/5 | |||
240 V | 30/15 | 30/15 | |||||
DC | 250 V | 7.5/4 | - | 7.5/4 | - |
Note 1: For 3-contact products, use two contacts.
Note: NF125-CV for 2 and 3 contacts only, and motor breaker for 3 contacts only.
Part Number |
---|
NF250-CV 3P 225A |
NF250-CV 3P 250A |
Part Number | Price | Name | Minimum Order Qty. | Volume Discount | Days to Ship | Ampere frame | Rated block capacity AC 200 V (kA) | Rated Current (A) | Connection Method |
---|---|---|---|---|---|---|---|---|---|
฿ 5,502.00 ฿ 4,126.50 | MOLDED CASE CIRCUIT BREAKER | 1 Piece(s) | Same day | [200AF to 399AF] 225AF | 36 | 225 | Surface type | ||
฿ 5,502.00 ฿ 4,126.50 | MOLDED CASE CIRCUIT BREAKER | 1 Piece(s) | Same day | [200AF to 399AF] 250AF | - | 250 | Surface type |
Loading...
Rated block capacity AC 400 V(kA) | 25 | Rated Braking Capacity at Rated Voltage of VDC 250(kA) | 15 | Number of Poles | 3 |
---|---|---|---|---|---|
Mounting Method | Fasten With Screws | Representative Standard | CE / TUV / CCC | Dimension height(mm) | 165 |
Dimension width(mm) | 105 | Dimension depth(mm) | 92 | Format | Economical Products |