(!) Since support from Microsoft will end on January 14 2020, Windows 7 user might not be able to use MISUMI website effectively. Please consider to update your system as ‘MISUMI Website system requirement’.
Select part number to Order Now/ Add to Cart
CC-Link remote I/O unit.
[Features]
· Positive/negative common shared type.
[Applications]
· Convenient for connections with field networks.
Outline drawing (unit: mm)
Transmission Speed | 156 kbps / 625 kbps / 2.5 Mbps / 5 Mbps / 10 Mbps (Selectable) | ||
---|---|---|---|
Maximum Total Cable Extension (Maximum Transmission Distance) | Ver. 1.10 | At 156 kbps | 1,200 m |
At 635 kbps | 900 m | ||
At 2.5 Mbps | 400 m | ||
At 5 Mbps | 160 m | ||
At 10 Mbps | 100 m | ||
Station Type | Master Station (Ver. 1 Master Station or Ver. 2 Master Station) Local Station (Ver. 1 Local Station or Ver. 2 Local Station) | ||
Maximum Number Of Connected Devices | Master Station | 64 devices | |
Number Of Occupied Stations | Local Station | 1 to 4 stations | |
Maximum Link Points Per System | CC-Link Ver. 1 | Remote inputs/outputs (RX, RY): 2,048 points Remote registers (RWw): 256 points Remote registers (RWr): 256 points | |
CC-Link Ver. 2 | Remote inputs/outputs (RX, RY): 8,192 points Remote registers (RWw): 2,048 points Remote registers (RWr): 2,048 points | ||
Link Points Per Station | CC-Link Ver. 1 | Remote inputs/outputs (RX, RY): 32 points (30 points for local stations) Remote registers (RWw): 4 points Remote registers (RWr): 4 points | |
CC-Link Ver. 2 | Expanded Cyclic Setting: × 1 Setting | Remote inputs/outputs (RX, RY): 32 points (30 points for local stations) Remote registers (RWw): 4 points Remote registers (RWr): 4 points | |
Expanded Cyclic Setting: × 2 Setting | Remote inputs/outputs (RX, RY): 32 points (30 points for local stations) Remote registers (RWw): 8 points Remote registers (RWr): 8 points | ||
Expanded Cyclic Setting: × 4 Setting | Remote inputs/outputs (RX, RY): 64 points (62 points for local stations) Remote registers (RWw): 16 points Remote registers (RWr): 16 points | ||
Expanded Cyclic Setting: × 8 Setting | Remote inputs/outputs (RX, RY): 128 points (126 points for local stations) Remote registers (RWw): 32 points Remote registers (RWr): 32 points | ||
Communication Method | Broadcast polling method | ||
Synchronization Method | Frame Synchronization Method | ||
Encryption Method | NRZI (Non Return to Zero Inverted) sign | ||
Transmission Path Type | Bus (RS-485) | ||
Transmission Format | HDLC Compliant | ||
Error Control Method | CRC (X16 + X12 + X5 + 1) | ||
Communication Cable | Dedicated CC-Link cable compatible with Ver. 1.10 Dedicated CC-Link cable (compatible with Ver. 1.00) Dedicated CC-Link high-performance cable (compatible with Ver. 1.00) | ||
Number Of Occupied Inputs/Outputs | 32 points (I/O assignment: Intelligent 32 points) | ||
5 V DC Internal Current Consumption | 0.46 A | ||
External Dimensions | Height (H) | 98 mm | |
Width (W) | 27.4 mm | ||
Depth (D) | 90 mm | ||
Mass | 0.12 kg |
Part Number |
---|
QJ61BT11N |
Part Number | Price | Name | Minimum Order Qty. | Volume Discount | Days to Ship |
---|---|---|---|---|---|
฿ 7,803.00 ฿ 5,202.26 | PLC(CPU UNIT) | 1 Piece(s) | Same day |
Loading...
Type of unit | CC-Link Ver. 2 Compatible | Applicable stations | Master station/local station |
---|
Please check the type/dimensions/specifications of the part QJ61BT11N in the MELSEC-Q Series Sequencer CC-Link System Master / Local Unit series.