(!) Since support from Microsoft will end on January 14 2020, Windows 7 user might not be able to use MISUMI website effectively. Please consider to update your system as ‘MISUMI Website system requirement’.
Select part number to Order Now/ Add to Cart
The miniature circuit breakers of the System pro M compact® series S 200 provide state-of-the-art safety and comfort. They stand out due to their high performance and the wide range of accessories and approvals.
The additional electrical currents 80 A and 100 A complement the current portfolio of the System pro M compact® and offer maximum performance in a single module width.
• Clear contact position indication in red/green (“real CPI”)
• Unique, patented twin terminal with captive screws and an increased opening for cables up to max. 50 mm2, finger-proof (IP20)
• Busbar slot in the back for best visibility during installation
• High performance in building installations and industrial applications up to 6 kA at Ue = 400 V AC acc. to IEC/EN 60947-2 and IEC/EN 60898-1
• Individual product identification code
• Approved acc. to IEC/EN 60898-1 and IEC/EN 60947-2 for global use
Part Number |
---|
S201-C80 |
Part Number | Price | Name | Minimum Order Qty. | Volume Discount | Days to Ship | Rated Braking Capacity at Rated Voltage of VDC 250 (kA) | Rated Current (A) | Height (mm) | Width (mm) | Power Loss | Weight (kg) | Operational Voltage | Rated Short-Circuit Capacity | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | Rated Conditional Short-Circuit Current (Inc) | Rated Service Short-Circuit Breaking Capacity (Ics) | Width in Number of Modular Spacings |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
฿ 1,716.67 | MINIATURE CIRCUIT BREAKER | 1 Piece(s) | 76 Day(s) | acc. to IEC 60898-1 230 / 400 V AC acc. to IEC 60898-1 230 V acc. to IEC 60947-2 230 V AC | 80 | 85 | 17.5 | 19.6 W at Rated Operating Conditions per Pole: 9.8 W | 0.125 | Maximum (Incl. Tolerance) 253 / 440 V AC Maximum (Incl. Tolerance) 60 V DC Minimum 12 V AC Minimum 12 V DC | (AC) 6 kA / (DC) 6 kA / (60 V DC) 6 kA / (230 / 400 V AC) 6 kA | (230 V AC) 6 kA / (230 V) 6 kA / (400 V AC) 10 kA | (230 V) 10 kA / (400 V) 10 kA | (230 V AC) 6 kA | 1 |
Loading...
Depth(mm) | 69 | Number of Poles | 1 | Tripping Characteristics | Type C |
---|---|---|---|---|---|
Standards | IEC/EN 60898-1 / IEC/EN 60947-2 | Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 440 V | Rated Impulse Withstand Voltage (Uimp) | 4 kV / at Sea Level 6.2 kV / at 2000 m 5 kV |
Dielectric Test Voltage | 50/60 Hz, 1 min: 2 kV | Input Voltage Type | AC | Rated Frequency (f)(Hz) | 50 / 60 |
Power Supply Connection | Arbitrary | Contact Position Indication | ON / OFF | Energy Limiting Class | 3 |
Electrical Durability | 10000 AC cycle | Mechanical Durability | 20000 cycle | Number of Protected Poles | 1 |
Overvoltage Category | III | Tightening Torque | 3 N·m | Actuator Type | Toggle |
Screw Terminal Type | Failsafe Bi-directional Cylinder-lift Terminal | Actuator Marking | I / O | Actuator Material | Insulation Group II, Black, Sealable |
Housing Material | Insulation Group I, RAL 7035 | Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
Mounting Position | any |
Recommended Screw Driver | Pozidriv 2 | Accessories Available | Yes | Connecting Capacity | Busbar 16 / 16 mm² Conductor 2.5 ... 50 mm² Flexible 4 ... 35 mm² Rigid 2.5 ... 50 mm² Stranded 2.5 ... 50 mm² |
Installation Size | acc. to DIN 43880 1 | Terminal Type | Screw Terminals | Built-In Depth (t2)(mm) | 69 |
Please check the type/dimensions/specifications of the part S201-C80 in the ABB Miniature Circuit Breaker System Pro M Compact® S 200 Series (80A-100A) C Characteristic series.
Part Number |
---|
S201-C100 |
S203-C100 |
S203-C80 |
Part Number | Price | Minimum Order Qty | Volume Discount | Days to Ship | Rated Braking Capacity at Rated Voltage of VDC 250 (kA) | Rated Current (A) | Height (mm) | Width (mm) | Power Loss | Weight (kg) | Operational Voltage | Rated Short-Circuit Capacity | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | Rated Conditional Short-Circuit Current (Inc) | Rated Service Short-Circuit Breaking Capacity (Ics) | Width in Number of Modular Spacings |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
฿ 1,716.67 | 1 Piece(s) | 76 Day(s) | acc. to IEC 60898-1 230 / 400 V AC acc. to IEC 60898-1 230 V acc. to IEC 60947-2 230 V AC | 100 | 85 | 17.5 | 9.8 W at Rated Operating Conditions per Pole: 9.8 W | 0.125 | Maximum (Incl. Tolerance) 253 / 440 V AC Maximum (Incl. Tolerance) 60 V DC Minimum 12 V AC Minimum 12 V DC | (230 / 400 V AC) 6 kA / (DC) 6 kA / (AC) 6 kA / (60 V DC) 6 kA | (230 V) 6 kA / (230 V AC) 6 kA / (400 V AC) 10 kA | (400 V) 10 kA / (230 V) 10 kA | (230 V AC) 6 kA | 1 | ||
฿ 4,833.33 | 1 Piece(s) | 76 Day(s) | acc. to IEC 60898-1 400 V AC acc. to IEC 60898-1 400 V acc. to IEC 60947-2 400 V AC | 100 | 88 | 52.5 | 29.4 W at Rated Operating Conditions per Pole: 9.8 W | 0.42 | Maximum (Incl. Tolerance) 440 V AC Minimum 12 V AC | (400 V) 6 kA / (DC) 6 kA / (400 V AC) 6 kA / (AC) 6 kA / (230 V AC) 6 kA | (400 V AC) 6 kA / (230 V AC) 10 kA / (400 V) 6 kA | (400 V) 20 kA / (230 V) 10 kA | (400 V AC) 6 kA | 3 | ||
฿ 4,833.33 | 1 Piece(s) | 76 Day(s) | acc. to IEC 60898-1 400 V AC acc. to IEC 60898-1 400 V acc. to IEC 60947-2 400 V AC | 80 | 88 | 52.5 | 39.2 W at Rated Operating Conditions per Pole: 9.8 W | 0.42 | Maximum (Incl. Tolerance) 440 V AC Minimum 12 V AC | (400 V) 6 kA / (DC) 6 kA / (400 V AC) 6 kA / (AC) 6 kA / (230 V AC) 6 kA | (400 V AC) 6 kA / (230 V AC) 10 kA / (400 V) 6 kA | (400 V) 20 kA / (230 V) 10 kA | (400 V AC) 6 kA | 3 |
How can we improve?
How can we improve?