Program Relay ZEN

Brand :
OMRON

Caution

    Product Description

    Simple programmable relay.
    [Features]
    ·ZEN, which is ideal for simple control, has been upgraded and renewed.
    ·Full of functions in a compact body (width 70 mm × length 90 mm).
    · A single unit combining relay, timer, counter, and time switch functionality.
    · No need to individually wire the timer and relay etc., greatly reducing the amount of wiring steps.
    · Multiple-day operation and pulse operation have been added. Time control settings are easy to configure, without complicated programming.
    · RS-485 communications types also available as part of the product series. Can remotely monitor the ZEN control status.
    · Features a counter function that can count up to 8 digits. The maximum count for DC power supply models is 150 Hz.
    · The twin-timer function allows you to set ON and OFF times separately, greatly simplifying repetitive operations. Helps reduce the program capacity.

    Specification Table of OMRON Other Relays

    ZEN external appearance

    Programmable Relay ZEN: related images

    OMRON Other Relays Rating

    FormatModel ZEN-□C□AR-A-V2 / Model ZEN-8E1ARModel ZEN-□C□D□-D-V2 / Model ZEN-8E1D□
    Power Supply Voltage100 to 240 V AC 50/60 Hz12 to 24 V DC (ripple inclusion rate 5% or less)
    Allowable Power Supply Voltage85 to 264 V AC10.8 to 28.8 V DC
    Power ConsumptionCPU unit (single unit)
    · Model ZEN-10C1AR-A-V2 / Model ZEN-10C2AR-A-V2/
    Model ZEN-10C3AR-A-V2
    5 VA or less (100 V AC), 7 VA or less (240 V AC)
    · Model ZEN-10C4AR-A-V2
    6 VA or less (100 V AC), 8 VA or less (240 V AC)
    · Model ZEN-20C□AR-A-V2
    7 VA or less (100 V AC), 10 VA or less (240 V AC)

    CPU unit (with 3 × expansion I/O units connected)
    · Model ZEN-10C1AR-A-V2 / Model ZEN-10C2AR-A-V2
    6 VA or less (100 V AC), 8 VA or less (240 V AC)
    · Model ZEN-10C4AR-A-V2
    7 VA or less (100 V AC), 9 VA or less (240 V AC)
    · Model ZEN-20C□AR-A-V2
    8 VA or less (100 V AC), 11 VA or less (240 V AC)

    Expansion I/O unit
    · Model ZEN-8E1AR
    3 VA or less (100 V AC), 4 VA or less (240 V AC)
    CPU Unit (single unit)
    · Model ZEN-10C□DR-D-V2 3W or less (12/24 V DC)
    (Model ZEN-10C3DR-D-V2 is 2.8 W or less)
    · Model ZEN-10C□DT-D-V2 is 2 W or less (12/24 V DC)
    · Model ZEN-20C□DR-D-V2 is 4 W or less (12/24 V DC)
    · Model ZEN-20C□DT-D-V2 is 2 W or less (12/24 V DC)

    CPU unit (with 3 × expansion I/O units connected)
    · Model ZEN-10C□DR-D-V2 is 4 W or less (12/24 V DC)
    · Model ZEN-10C□DT-D-V2 is 3 W or less (12/24 V DC)
    · Model ZEN-20C□DR-D-V2 is 5 W or less (12/24 V DC)
    · Model ZEN-20C□DT-D-V2 is 3 W or less (12/24 V DC)

    Expansion I/O unit
    · Model ZEN-8E1DR is 2 W or less (12/24 V DC)
    Inrush CurrentModel ZEN-10C□AR-A-V2: 4.5 A or less
    Model ZEN-20C□AR-A-V2: 4.5 A or less
    Model ZEN-8E1AR: 4 A or less
    Model ZEN-10C□D□-D-V2: 30 A or less
    Model ZEN-20C□D□-D-V2: 30 A or less
    Model ZEN-8E1DR: 15 A or less
    Ambient Operating Temperature0 to +55°C (LED type is −25 to +55°C)
    Ambient Storage Temperature−20 to +75°C(For LED type, −40 to +75°C)
    Ambient Operating Humidity10 to 90% RH (assuming no condensation)
    Operating Ambient AtmosphereMust be no corrosive gas
    Mounting MethodSurface mounting, DIN rail mounting (standard mounting, upward mounting)*
    Terminal BlockTerminal block for solid wire (use solid wire or strand wire)
    Terminal block tightening torque0.565 to 0.6 N·m (5 to 5.3 in-lb)
    Protective StructureIP20 (built-into panel type)
    • *1. Other Relays, Can be mounted on 35-mm DIN track.

    OMRON Other Relays Performance

    Control MethodStored program method
    Input/Output Control MethodCyclic scan method
    Programming LanguageLadder diagram
    Program Capacity96 lines (3 × input conditions and 1 × output per line)
    Maximum Number Of Control I/O Points44 points—CPU Units with 20 I/O points: 12 inputs and 8 outputs *1
    Expansion I/O Units: 4 inputs and 4 outputs each, × 3 Units
    LCD Display *212 digits (characters) × 4 lines, with backlight
    Operation Buttons *28 (4 × cursor buttons and × 4 operation buttons)
    User Program RetentionCPU-Unit Built-In Internal EEPROM, Memory Cassette (optional)
    Power Interruption HoldInternal holding relay status, holding timer/counter present values, calendar and clock (year, month, day of month, day of week, time)
    · Super capacitor backup time: 2 days or more (25°C)
    · Life of optional battery life: 10 years or more (25°C)
    Calendar and clock function *2Time accuracy: ±15 secs per month (25°C)
    Maximum Counting Speed150 Hz: 8-digit counter (F) set to high-speed operations (with DC power supplies only) *3
    Timer accuracy*40.01 secs unit: −0.05% −10 ms max.
    min/s unit: −0.05% −1 s max.
    h/min unit: −0.05% −1 min max.
    Insulation ResistanceBetween power supply terminal and batch input terminals − batch output terminals, between mutual output terminals
    Between all terminals of the CPU unit − all terminals of the expansion I/O unit: 20 MΩ min. (with 500 V DC ohmmeter)
    Insulation· Reinforced insulation
    Between power supply or input terminals and output terminals, Between terminals of different output circuits, Between all terminals of the CPU unit and all terminals of the expansion I/O unit
    · No separation
    Between power supply and input terminals of the same unit, Between power supply terminals of CPU Unit and PC connector
    Between battery unit connector, or all expansion unit connectors
    Dielectric StrengthBetween power supply terminal and batch input terminals − batch output terminals, between mutual output terminals
    Between all terminals of the CPU unit − all terminals of the expansion I/O unit: 2,300 V AC, 50/60 Hz for 1 min. (leakage current 1 mA max.)
    Vibration ResistanceConforms to IEC60068-2-6, 5 to 9 Hz with 3.5-mm single amplitude, 9 to 150 Hz acceleration 9.8 m/s2, 10 sweeps each in X, Y, and Z directions (1 octave/min)
    Shock ResistanceConforms to IEC60068-2-27, 147 m/s2, 3 times each in X, Y, and Z directions
    Weight10 I/O point type: approx. 300 g max, 20 I/O point type: approx. 350 g max, Expansion I/O unit: approx. 120 g

    *1. Other Relays, Up to 34 points for CPU units with 10 I/O points. With communications-type CPU Units, however, the CPU Unit has 6 inputs and 3 outputs, for a maximum of 33 I/O points.
    *2. Other Relays, Not provided for LED-type CPU unit without display (Model ZEN-□C2□□-□-V2).
    *3. Other Relays, 150 Hz or less with a large ladder program capacity. For details, see "8-Digit Counter Operations" in the catalog.
    *4. Other Relays, -0.05% is the ratio relative to the set value.

    Model Configuration of OMRON Other Relays

    Programmable Relay ZEN: related images

    Note 1. Other Relays, Up to 3 expansion I/O units can be connected (excluding economy type CPU units). Note that AC input type expansion I/O units cannot be connected to a DC power supply type CPU unit.
    Note 2. Other Relays, The PC connection cable and memory cassette cannot be equipped at the same time.
    Note 3. Other Relays, On the LED (no LCD) type, a program cannot be formed with just the CPU single unit, so support software or a memory cassette will be necessary.

    • *See the OMRON Other Relays catalog for communication functions, applicable standards, and dimensional outline drawings.
    Viewed Products
    Recently Viewed Products
    My Components
    My Components
    0
    Cart
    Cart
    Economy Series
    MRO Product

    Chat with MISUMI

    Chat service is available for any inquiry to MISUMI

    Service hours

    9:00 - 18:00 (Mon-Sat)

    For out of service hours, you can leave a message to us.
    We will reply to your inquiries on the next business day.
    (except Sundays and public holidays).

    Noted for use

    Chat service is for Corporate customers and limited for Thai language.

    Request for Quotation and Place Order is not available on Chat.

    Start chat