Program Relay ZEN

Caution
Product Description
Simple programmable relay.
[Features]
·ZEN, which is ideal for simple control, has been upgraded and renewed.
·Full of functions in a compact body (width 70 mm × length 90 mm).
· A single unit combining relay, timer, counter, and time switch functionality.
· No need to individually wire the timer and relay etc., greatly reducing the amount of wiring steps.
· Multiple-day operation and pulse operation have been added. Time control settings are easy to configure, without complicated programming.
· RS-485 communications types also available as part of the product series. Can remotely monitor the ZEN control status.
· Features a counter function that can count up to 8 digits. The maximum count for DC power supply models is 150 Hz.
· The twin-timer function allows you to set ON and OFF times separately, greatly simplifying repetitive operations. Helps reduce the program capacity.
Specification Table of OMRON Other Relays
ZEN external appearance

OMRON Other Relays Rating
| Format | Model ZEN-□C□AR-A-V2 / Model ZEN-8E1AR | Model ZEN-□C□D□-D-V2 / Model ZEN-8E1D□ |
|---|---|---|
| Power Supply Voltage | 100 to 240 V AC 50/60 Hz | 12 to 24 V DC (ripple inclusion rate 5% or less) |
| Allowable Power Supply Voltage | 85 to 264 V AC | 10.8 to 28.8 V DC |
| Power Consumption | CPU unit (single unit) · Model ZEN-10C1AR-A-V2 / Model ZEN-10C2AR-A-V2/ Model ZEN-10C3AR-A-V2 5 VA or less (100 V AC), 7 VA or less (240 V AC) · Model ZEN-10C4AR-A-V2 6 VA or less (100 V AC), 8 VA or less (240 V AC) · Model ZEN-20C□AR-A-V2 7 VA or less (100 V AC), 10 VA or less (240 V AC) CPU unit (with 3 × expansion I/O units connected) · Model ZEN-10C1AR-A-V2 / Model ZEN-10C2AR-A-V2 6 VA or less (100 V AC), 8 VA or less (240 V AC) · Model ZEN-10C4AR-A-V2 7 VA or less (100 V AC), 9 VA or less (240 V AC) · Model ZEN-20C□AR-A-V2 8 VA or less (100 V AC), 11 VA or less (240 V AC) Expansion I/O unit · Model ZEN-8E1AR 3 VA or less (100 V AC), 4 VA or less (240 V AC) | CPU Unit (single unit) · Model ZEN-10C□DR-D-V2 3W or less (12/24 V DC) (Model ZEN-10C3DR-D-V2 is 2.8 W or less) · Model ZEN-10C□DT-D-V2 is 2 W or less (12/24 V DC) · Model ZEN-20C□DR-D-V2 is 4 W or less (12/24 V DC) · Model ZEN-20C□DT-D-V2 is 2 W or less (12/24 V DC) CPU unit (with 3 × expansion I/O units connected) · Model ZEN-10C□DR-D-V2 is 4 W or less (12/24 V DC) · Model ZEN-10C□DT-D-V2 is 3 W or less (12/24 V DC) · Model ZEN-20C□DR-D-V2 is 5 W or less (12/24 V DC) · Model ZEN-20C□DT-D-V2 is 3 W or less (12/24 V DC) Expansion I/O unit · Model ZEN-8E1DR is 2 W or less (12/24 V DC) |
| Inrush Current | Model ZEN-10C□AR-A-V2: 4.5 A or less Model ZEN-20C□AR-A-V2: 4.5 A or less Model ZEN-8E1AR: 4 A or less | Model ZEN-10C□D□-D-V2: 30 A or less Model ZEN-20C□D□-D-V2: 30 A or less Model ZEN-8E1DR: 15 A or less |
| Ambient Operating Temperature | 0 to +55°C (LED type is −25 to +55°C) | |
| Ambient Storage Temperature | −20 to +75°C(For LED type, −40 to +75°C) | |
| Ambient Operating Humidity | 10 to 90% RH (assuming no condensation) | |
| Operating Ambient Atmosphere | Must be no corrosive gas | |
| Mounting Method | Surface mounting, DIN rail mounting (standard mounting, upward mounting)* | |
| Terminal Block | Terminal block for solid wire (use solid wire or strand wire) | |
| Terminal block tightening torque | 0.565 to 0.6 N·m (5 to 5.3 in-lb) | |
| Protective Structure | IP20 (built-into panel type) | |
- *1. Other Relays, Can be mounted on 35-mm DIN track.
OMRON Other Relays Performance
| Control Method | Stored program method |
|---|---|
| Input/Output Control Method | Cyclic scan method |
| Programming Language | Ladder diagram |
| Program Capacity | 96 lines (3 × input conditions and 1 × output per line) |
| Maximum Number Of Control I/O Points | 44 points—CPU Units with 20 I/O points: 12 inputs and 8 outputs *1 Expansion I/O Units: 4 inputs and 4 outputs each, × 3 Units |
| LCD Display *2 | 12 digits (characters) × 4 lines, with backlight |
| Operation Buttons *2 | 8 (4 × cursor buttons and × 4 operation buttons) |
| User Program Retention | CPU-Unit Built-In Internal EEPROM, Memory Cassette (optional) |
| Power Interruption Hold | Internal holding relay status, holding timer/counter present values, calendar and clock (year, month, day of month, day of week, time) · Super capacitor backup time: 2 days or more (25°C) · Life of optional battery life: 10 years or more (25°C) |
| Calendar and clock function *2 | Time accuracy: ±15 secs per month (25°C) |
| Maximum Counting Speed | 150 Hz: 8-digit counter (F) set to high-speed operations (with DC power supplies only) *3 |
| Timer accuracy*4 | 0.01 secs unit: −0.05% −10 ms max. min/s unit: −0.05% −1 s max. h/min unit: −0.05% −1 min max. |
| Insulation Resistance | Between power supply terminal and batch input terminals − batch output terminals, between mutual output terminals Between all terminals of the CPU unit − all terminals of the expansion I/O unit: 20 MΩ min. (with 500 V DC ohmmeter) |
| Insulation | · Reinforced insulation Between power supply or input terminals and output terminals, Between terminals of different output circuits, Between all terminals of the CPU unit and all terminals of the expansion I/O unit · No separation Between power supply and input terminals of the same unit, Between power supply terminals of CPU Unit and PC connector Between battery unit connector, or all expansion unit connectors |
| Dielectric Strength | Between power supply terminal and batch input terminals − batch output terminals, between mutual output terminals Between all terminals of the CPU unit − all terminals of the expansion I/O unit: 2,300 V AC, 50/60 Hz for 1 min. (leakage current 1 mA max.) |
| Vibration Resistance | Conforms to IEC60068-2-6, 5 to 9 Hz with 3.5-mm single amplitude, 9 to 150 Hz acceleration 9.8 m/s2, 10 sweeps each in X, Y, and Z directions (1 octave/min) |
| Shock Resistance | Conforms to IEC60068-2-27, 147 m/s2, 3 times each in X, Y, and Z directions |
| Weight | 10 I/O point type: approx. 300 g max, 20 I/O point type: approx. 350 g max, Expansion I/O unit: approx. 120 g |
*1. Other Relays, Up to 34 points for CPU units with 10 I/O points. With communications-type CPU Units, however, the CPU Unit has 6 inputs and 3 outputs, for a maximum of 33 I/O points.
*2. Other Relays, Not provided for LED-type CPU unit without display (Model ZEN-□C2□□-□-V2).
*3. Other Relays, 150 Hz or less with a large ladder program capacity. For details, see "8-Digit Counter Operations" in the catalog.
*4. Other Relays, -0.05% is the ratio relative to the set value.
Model Configuration of OMRON Other Relays

Note 1. Other Relays, Up to 3 expansion I/O units can be connected (excluding economy type CPU units). Note that AC input type expansion I/O units cannot be connected to a DC power supply type CPU unit.
Note 2. Other Relays, The PC connection cable and memory cassette cannot be equipped at the same time.
Note 3. Other Relays, On the LED (no LCD) type, a program cannot be formed with just the CPU single unit, so support software or a memory cassette will be necessary.
- *See the OMRON Other Relays catalog for communication functions, applicable standards, and dimensional outline drawings.