ø16 X6 Series, Emergency Stop Button Switch

Caution
Product Description
Uses a "safety potential construction" for excellent safety.
[Features]
· Uses the third-generation "safety potential construction" for excellent safety.
· One of the smallest emergency stop push button switches in the world.
· Button sizes come in two types: ø30 and ø40.
· Buttons come in "emergency stop" red and "stop" yellow.
· 2 types of reset operations supported (push-lock-pull or turn-reset).
· UL/c-UL-approved and EN standard compliant.
· Safety lock feature (IEC60947-5-5: 6.2).
· Direct circuit control function (IEC60947-5-5: 5.2, IEC60947-5-1 appendix K compliant).
· IP65 protective construction (IEC60529)
Specification Table of IDEC Emergency Stop Switches / Safety Switches
Model number (plain type) of IDEC Emergency Stop Switches / Safety Switches
Emergency Stop Switches / Safety Switches, Push lock, pull or turn reset switch

Appearance of φ30 (diameter 30 mm) medium-sized button

Appearance of φ40 (diameter 40 mm) large button
| Product name | Main contact (b contact) | Solder terminal type |
|---|---|---|
| Model number (order number) | ||
| Medium size (φ30) button | 1b | AB6E-3BV01PRH |
| 2b | AB6E-3BV02PRH | |
| Large (φ40) button | 1b | AB6E-4BV01PRH |
| 2b | AB6E-4BV02PRH |
The push-lock, pull or turn reset type is locked in place when the button is pressed and can be reset by pulling the button or turning it to the right.
Model number (arrow type) of IDEC Emergency Stop Switches / Safety Switches
Emergency Stop Switches / Safety Switches, Push lock, pull or turn reset switch

Appearance of φ30 (diameter 30 mm) medium-sized button

Appearance of φ40 (diameter 40 mm) large button
| Product name | Main contact (b contact) | Solder terminal type |
|---|---|---|
| Model number (order number) | ||
| Medium size (φ30) button | 1b | AB6E-3BV01PRM |
| 2b | AB6E-3BV02PRM | |
| Large (φ40) button | 1b | AB6E-4BV01PRM |
| 2b | AB6E-4BV02PRM |
The push-lock, pull or turn reset type is locked in place when the button is pressed and can be reset by pulling the button or turning it to the right.
Specification of IDEC Emergency Stop Switches / Safety Switches
| Applicable Standards | IEC60947-5-1, EN60947-5-1 IEC60947-5-5 (Note), EN60947-5-5 (Note) JIS C8201-5-1, JIS C8201-5-5, UL508 CSA C22.2 No.14, GB14048.5 |
|---|---|
| Standard use condition | Ambient temperature: -25 to +60°C (but do not freeze) Ambient humidity: 45 to 85% RH (but do not condense) Storage temperature: -45 to +80°C (but do not freeze) |
| Operating force (initial value) | Push lock: 10.5N Pull reset: 8.8N Turn reset: 0.17N・m |
| Minimum direct opening force | 40N |
| Minimum operating distance to minimum direct opening function | 4.5mm |
| Maximum Operating Distance | 4.5mm |
| Contact Resistance | 50mΩ or less (initial value) |
| Insulation resistance | 100MΩ or more (at DC500V mega) |
| Overvoltage Category | II |
| Impulse withstand voltage | 2.5kV |
| Pollution level | 3 |
| Opening and closing frequency | 900 times/hour |
| Shock Resistant | Malfunction: 150m/s2 Endurance: 1000m/s2 |
| Vibration resistance | Malfunction: 10 to 500 Hz, half amplitude 0.35 mm, acceleration 50 m/s2 Durability: 10 to 500 Hz, half amplitude 0.35 mm, acceleration 50 m/s2 |
| Durability | Mechanical: 100,000 times or more Electrical: 100,000 times or more |
| Protective structure | IP65 (IEC 60529) |
| Short Circuit Protection Device | 250V/10A fuse (Type aM IEC60269-1/IEC60269-2) |
| Conditional Short Circuit Current | 1000A |
| Terminal Shape | Solder terminals Solder and tab 110 terminals |
| Recommended tightening torque for lock nuts | 0.88N・m |
| Connectable wires | 1.25mm2or less (AWG16 or less) |
| Terminal soldering conditions | 310-350℃, within 3 seconds |
| Weight (approx.) | Medium: 13g, Large: 16g |
Contact Rating of IDEC Emergency Stop Switches / Safety Switches
| Rated insulation voltage (Ui) | 250V | |||||
|---|---|---|---|---|---|---|
| Rated current (Ith) | 5A | |||||
| Rated operating voltage (Ue) | 30V | 125V | 250V | |||
| Rated Operating Current* | Main Contact | AC 50/60Hz | Resistive load (AC-12) | - | 5A | 3A |
| Inductive load (AC-15) | - | 1.5A | 0.75A | |||
| Direct current | Resistive Load (DC-12) | 2A | 0.4A | 0.2A | ||
| Inductive Load (DC-13) | 1A | 0.22A | 0.1A | |||
- Emergency Stop Switches / Safety Switches, Minimum applicable load (reference value) = AC/DC 5V/1mA (The usable range may vary depending on the operating conditions and type of load.)
- The operating current is indicated according to the type of making and breaking current capacity in accordance with JIS C8201-5-1.
*TÜV/CCC certification rating: AC-15 0.75A/250V, DC-13 1A/30V
UL certification rating: Standard Duty AC 0.75A/250V
Standard Duty DC 1A/30V
Features of IDEC Emergency Stop Switches / Safety Switches

Emergency Stop Switches / Safety Switches, The rounded, smooth design prevents dust and other particles from sticking to it and makes it easy to wipe off dirt.