Fuse Link CLS for capacitors

Caution
Product Description
CLS Type Fuse Link For Motor and Capacitor Switching.
[Features]
· Small size with a large breaking capacity and load capacity.
· Withstands large starting current, including the particularly frequent on/off.
· Extremely quickly interrupted when short-circuited, with superior current-limiting characteristics.
· Operation overvoltage is particularly low.
· Optimal severing characteristics (M type) for motor use.
· Fuse link has an airtight structure and an operating display device.
[Applications]
· Switch function.
High Voltage / Special High Voltage Current-Limiting Fuse, CLS Type Fuse Link Specifications

CLS Type Fuse Link Appearance

CLS type (model number R) fuse holder 3.6 kV M100A dimensional drawing, unit: mm

CLS type (model number R) fuse holder 3.6 kV M200A dimensional drawing, unit: mm

CLS type (model number R) fuse holder 7.2 kV M50A dimensional drawing, unit: mm

CLS type (model number R) fuse holder 7.2 kV M200A dimensional drawing, unit: mm

CLS type (model number R) fuse holder 7.2 kV M400A dimensional drawing, unit: mm
CLS Type Fuse Rating And Type
| Fuse Link | Fuse Holder (Indoor) | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Main Use | Usage Location | Type Name | Model Number | Rated Voltage kV | Rated Current A | Rated Break Current kA | Type Name | Model Number | Rated Voltage kV | Rated Current A | Rated Impulse Withstand Voltage kV | |
| M | C | |||||||||||
| For electric motor For capacitor For frequent switch | Indoor | CLS | R | 3.6 | M20 | C15 | 40 | CLS | R | 3.6 | M100 | 45 |
| M50 | C35 | |||||||||||
| M100 | C70 | |||||||||||
| 3.6 | M150 | C100 | 40 | CLS | R | 3.6 | M200 | 45 | ||||
| M200 | C130 | |||||||||||
| 3.6 | M300 | C200 | 40 | CLS | R | 3.6 | M400 | 45 | ||||
| M400 | C300 | |||||||||||
| 7.2 | M20 | C15 | 40 | CLS | R | 7.2 | M50 | 60 | ||||
| M50 | C35 | |||||||||||
| 7.2 | M100 | C70 | 40 | CLS | R | 7.2 | M200 | 60 | ||||
| M150 | C100 | |||||||||||
| M200 | C130 | |||||||||||
| 7.2 | M300 | C200 | 40 | CLS | R | 7.2 | M400 | 60 | ||||
| M400 | C300 | |||||||||||
| PD | 3.6 | M20 | C15 | 40 | SCL, SCT type (Type number EHS2R) For load switch with fuse | |||||||
| M50 | C35 | |||||||||||
| P | M100 | C70 | SCL, SCT type (Type number EHF3R) For load switch with fuse (However, no striker) Note 2 | |||||||||
- Note 1:The CLS type (type number PD) fuse link has a striker, and can automatically trip a load switch with a SCL/T type (type number EHS2R) fuse.
- Note 2:The CLS type (type number P) fuse link has an operation display device, but cannot automatically trip a switch upon fuse operation using a load switch having an SCL/T type (type number EHF3R) fuse.
*Please refer to the catalog for any information not listed above.