GOT1000 CC-Link Communication Unit

Brand :
MITSUBISHI
Caution
- This product belongs in RoHS Directive under Category 9 "Monitoring and control equipment" with exclusion from the usage restriction of phthalate esters until 21 July 2021.
Product Description
CC-Link Communication Unit for GOT1000 Series.
[Features]
・ Intelligent device station module CC-Link Ver.2 compatible
・ Number of occupied stations 1 station/4 stations selectable
GOT1000 CC-Link Communication Unit Details

Product image of GT15-J61BT13
Dimensional Drawing of the Product
(Unit: mm)

GT15-J61BT13 dimensional drawing
Product Specifications
| Category | Communication unit | ||
|---|---|---|---|
| Series | GOT1000 | ||
| Unit | CC-Link Communication Unit | ||
| Product Type Name | GT15-J61BT13 | ||
| Applicable Standards | UL/cUL, CE(EMC), KC | ||
| Supported Models | GT27, GT25 (5.7 type, wide model, enhanced environmental resistance model are excluded), GT16, GT15 | ||
| CC-Link Station Type | Intelligent Device Station | ||
| Number of Occupied Stations | Possible to select 1 or 4 stations | ||
| Ver. 1 Mode | Maximum Link Points Per System | Remote inputs/outputs (RX, RY): 2,048 points, Remote registers (RWw): 256 points, Remote registers (RWr): 256 points | |
| Link Points Per Station | Remote inputs/outputs (RX, RY): 32 points, Remote registers (RWw): 4 points, Remote registers (RWr): 4 points | ||
| Number of Link Points Per Number of Occupied Stations | "One station occupied" Remote inputs/outputs (RX, RY): 32 points, Remote registers (RWw): 4 points, Remote registers (RWr): 4 points, "4 stations occupied" Remote inputs/outputs (RX, RY): 128 points, Remote registers (RWw): 16 points, Remote registers (RWr): 16 points | ||
| Ver. 2 Mode | Maximum Link Points Per System | Remote inputs/outputs (RX, RY): 8,192 points, Remote registers (RWw): 2,048 points, Remote registers (RWr): 2,048 points | |
| Link Points Per Station | Expanded Cyclic Setting: × 1 Setting | Remote inputs/outputs (RX, RY): 32 points, Remote registers (RWw): 4 points, Remote registers (RWr): 4 points | |
| Expanded Cyclic Setting: × 2 Setting | Remote inputs/outputs (RX, RY): 32 points, Remote registers (RWw): 8 points, Remote registers (RWr): 8 points | ||
| Expanded Cyclic Setting: × 4 Setting | Remote inputs/outputs (RX, RY): 64 points, Remote registers (RWw): 16 points, Remote registers (RWr): 16 points | ||
| Expanded Cyclic Setting: × 8 Setting | Remote inputs/outputs (RX, RY): 128 points, Remote registers (RWw): 32 points, Remote registers (RWr): 32 points | ||
| Number of Link Points Per Number of Occupied Stations | Expanded Cyclic Setting: × 1 Setting | "One station occupied" Remote inputs/outputs (RX, RY): 32 points, Remote registers (RWw): 4 points, Remote registers (RWr): 4 points, "4 stations occupied" Remote inputs/outputs (RX, RY): 128 points, Remote registers (RWw): 16 points, Remote registers (RWr): 16 points | |
| Expanded Cyclic Setting: × 2 Setting | "One station occupied" Remote inputs/outputs (RX, RY): 32 points, Remote registers (RWw): 8 points, Remote registers (RWr): 8 points, "4 stations occupied" Remote inputs/outputs (RX, RY): 224 points, Remote registers (RWw): 32 points, Remote registers (RWr): 32 points | ||
| Expanded Cyclic Setting: × 4 Setting | "One station occupied" Remote inputs/outputs (RX, RY): 64 points, Remote registers (RWw): 16 points, Remote registers (RWr): 16 points, "4 stations occupied" Remote inputs/outputs (RX, RY): 448 points, Remote registers (RWw): 64 points, Remote registers (RWr): 64 points | ||
| Expanded Cyclic Setting: × 8 Setting | "One station occupied" Remote inputs/outputs (RX, RY): 128 points, Remote registers (RWw): 32 points, Remote registers (RWr): 32 points, "4 stations occupied" Remote inputs/outputs (RX, RY): 896 points, Remote registers (RWw): 128 points, Remote registers (RWr): 128 points | ||
| Transmission Speed | 156 kbps / 625 kbps / 2.5 Mbps / 5 Mbps / 10 Mbps | ||
| Maximum Transmission Distance | Varies depending on the transmission speed. | ||
| Maximum Number of Connected Devices | 26 devices Maximum number of connected devices varies depending on the CC-Link system configuration used. For details of maximum number of connected devices, refer to CC-Link user’s manual (detailed version). | ||
| Connection Cable | CC-Link dedicated cable | ||
| Internal Current Consumption (5 V DC) | 0.56 A | ||
| Weight | 0.18 kg | ||
| Terminal Block | Screw Tightening Torque | Screw for wiring: 0.5 to 0.6 N·m Terminal block mounting screw: 0.7 to 0.8 N·m | |
| Recommended Driver | rStraight slot screwdriver (blade point thickness: 0.6 mm, width 3.5 mm) | ||
- *When mounting an expansion unit on the CC-Link Communication Unit, the ambient temperature for general specifications should be 5°C lower than the maximum temperature.
- *Remote input/output with the maximum link points per system: Input/output signals (RX, RY) occupy 16 points of system area within each device point.