Wiring cable for electronic equipment CL2/2464-3599-DS LF

Caution
Product Description
[Features]
· Uses cross-linked polyethylene for the insulator.
· Uses oil resistant, heat resistant and flexible vinyl sheath material.
· Controlled to a characteristic impedance of 100+/-15Ω (5 MHz) (differential).
· Compatible with UL VW-1 and cUL FT1 flame retardant.
· Passed the UL vertical tray flame retardant test.
[Applications]
· RS485 and RS422 compatible cable.
· Can also be used as a tray cable for signal and remote control.
· UL and cUL shared double shielded device cable, rated at 300 V and 80°C (categories: QPTZ, AVLV2, AVLV8).
· Listing standard CL2 has been acquired and NFPA70 and 79 are supported.
Compliant standards
| Certification | UL CL2 | UL AWM | cUL |
|---|---|---|---|
| Applicable Standards | UL 13 | UL 758 | CSA C22.2 No. 210 |
| Type symbol | CL2 | UL AWM Style 2464 | CSA AWM IIA |
| Rated voltage | 150V | 300V | 300V |
| Rated temperature | 75℃ | 80℃ | 80℃ |
| Conductor | UL 13 | UL 758 | CSA C22.2 No. 210 |
| Flame retardancy | Vertical Tray Flame Test | VW-1 | FT1 |

Specifications Table

Product Properties
Allowable current
- The allowable current is the value for a single cable installed in air at an ambient temperature of 30℃.
- The allowable current is calculated based on JCS0168.
- Multiply the following correction factor according to the ambient temperature.
Current reduction factor (for ambient temperature)
| Ambient temperature (℃) | 30 | 40 | 50 | 60 | 70 | 80 | 90 | 100 |
|---|---|---|---|---|---|---|---|---|
| Current Reduction Factor | 1.00 | 0.89 | 0.77 | 0.63 | 0.45 | - | - | - |
Wire Core Identification
Structure

Surface Printing

Identification


*The numbers inside the circles indicate the corresponding numbers in the identification table.
Identification table

White/black indicates a white line on a black insulator.
Standard sales length
100 m