CC-Link Analog Input/Output (Temperature Input)

Brand :
MITSUBISHI
Caution
- This product belongs in RoHS Directive under Category 9 "Monitoring and control equipment" with exclusion from the usage restriction of phthalate esters until 21 July 2021.
Product Description
Temperature input unit for an in-line field network CC-Link.
[Features]
· Screw / 2‑piece terminal block type.
[Applications]
· Convenient for equipment connection in a field network.
Various Specifications of CC-Link Analog Input/Output (Temperature Input)
CC-Link Platinum Resistance Temperature Detector Pt100 Temperature Input Unit

AJ65BT-64RD3
- 4 channels
- 3-wire platinum resistance temperature detector (Pt100, JPt100)
- Conversion speed: 40 ms / 1 channel
- 2-piece terminal block type
- Number of occupied stations: 4

AJ65BT-64RD4
- 4 channels
- 4-wire platinum resistance temperature detector (Pt100, JPt100)
- Conversion speed: 40 ms / 1 channel
- 2-piece terminal block type
- Number of occupied stations: 4
CC-Link Thermocouple Temperature Input Unit
CC-Link Temperature-sensing Resistance Input Unit

AJ65BT-68TD
- 8 channels
- Thermocouple (B, R, S, K, E, J, T)
- Conversion speed: 45 ms / 1 channel
- 2-piece terminal block type
- Number of occupied stations: 4

AJ65SBT2B-64RD3
- 4 channels
- 3-wire temperature-sensing resistance (Pt100, JPt100, Ni100)
- Conversion speed: 40 ms / 1 channel
- 2-piece terminal block type
- Number of occupied stations: 1
CC-Link Thermocouple Input Unit

AJ65SBT2B-64TD
- 4 channels
- Thermocouple (B, R, S, K, E, J, T, N)
- Conversion speed: 640 ms / 4 channels
- 2-piece terminal block type
- Number of occupied stations: 1
CC-Link Analog Input/Output (Temperature Input) Common Specifications
| Ambient Operating Temperature | 0 to 55°C | ||
|---|---|---|---|
| Ambient Storage Temperature | -20 to 75°C | ||
| Ambient Operating Humidity | 10 to 90% RH, non-condensing | ||
| Ambient Storage Humidity | 10 to 90% RH, non-condensing | ||
| Vibration Resistance | JIS B 3502, IEC 61131-2 Compliant | Under Intermittent Vibration | Frequency: 5 to 8.4 Hz, Amplitude: 3.5 mm Frequency: 8.4 to 150 Hz, Acceleration: 9.8 m/s2 Sweeps: 10 sweeps in each direction of X, Y and Z |
| Under Continuous Vibration | Frequency: 5 to 8.4 Hz, Amplitude: 1.75 mm Frequency: 8.4 to 150 Hz, Acceleration: 4.9 m/s2 | ||
| Impact Resistant | JIS B 3502, IEC 61131-2 compliant (147 m/s2, 3 times in 3 directions of X, Y and Z) | ||
| Operating Atmosphere | No corrosive gases | ||
| Operating Altitude | 0 to 2,000 m | ||
| Installation Location | Inside the control panel | ||
| Overvoltage Category | II or lower | ||
| Pollution Degree | 2 or less | ||