This air-cooled aftercooler does not require cooling equipment, and maintenance is easy without concerns about water supply cut-off or freezing.
[Features]
· Cools high temperature compressed air from a compressor down to 40°C or less and removes moisture from the air.
· Compact size and light weight.
· Uses minimal floor space.
· Built-in drain separator.
· Dust-protecting filter optional.
HAA15 external appearance
HAA7 external appearance
Working Principle
Model | HAA7 | HAA15 | HAA22 | HAA37 | ||||
---|---|---|---|---|---|---|---|---|
Rated conditions | Air flow capacity L/min (ANR)*1 | 1,000 | 2,200 | 3,300 | 5,700 | |||
Inlet air temperature (°C) | 70 | |||||||
Inlet air pressure (MPa) | 0.7 | |||||||
Ambient temperature (°C) | 32 | |||||||
Outlet air temperature (°C) | 40 | |||||||
Operating range | Applicable fluid | Compressed Air | ||||||
Inlet air temperature (°C) | 5 to 100 | |||||||
Inlet air pressure (MPa) | 0.05 to 1.0 (With auto drain: 0.15 to 1.0) | 0.05 to 0.97 (With auto drain: 0.15 to 0.97) | ||||||
Ambient temperature (°C) | 2 to 50 | |||||||
Installation location | Indoors | |||||||
Electric specifications | Power supply | Single-phase 100 V AC (50/60 Hz) | Single-phase 200 V AC (50/60 Hz) | Single-phase 100 V AC (50/60 Hz) | Three-phase 200 V AC (50/60 Hz) | Three-phase 200 V AC (50/60 Hz) | Three-phase 200 V AC (50/60 Hz) | |
Power consumption (W) | 50 Hz | 55 | 58 | 55 | 50 | 90 | 204 | |
60 Hz | 58 | 65 | 65 | 60 | 130 | 244 | ||
Current (A) | 50 Hz | 0.8 | 0.43 | 0.8 | 0.4 | 0.4 | 2.0 | |
60 Hz | 0.81 | 0.46 | 0.9 | 0.35 | 0.45 | 2.0 | ||
Proof pressure (MPa) | 1.5 | |||||||
Cooling fan diameter (mm) | 255 | 300 | 400 | 350 × 2 pcs. | ||||
Cooler | Aluminum plate tube with fins | |||||||
Port size for inlet/outlet air | Rp3/4 socket | 1B union | 1 1/2 B union | |||||
Port size for drain outlet piping (With auto drain) | Rc 3/8 (Rc 3/8) | Rc 1/2 (Rc 3/8) | ||||||
Weight (kg) | 18 | 24 | 36 | 55 | ||||
Coating color | Munsell N-8 (white), Munsell 2.5PB5/8.5 (blue) | |||||||
Applicable compressor (kW)*2 | 7.5 | 15 | 22 | 37 | ||||
Standard equipment | Thermometer for outlet air temperature (1 pc.) | - | ● | ● | ● | |||
Accessories*3 | Drain valve (1 pc.) | 3/8B | 1/2B | |||||
Union (2 pcs.) | - | 1B | 1 1/2 B |
*1: ANR is the value at 20°C, atmospheric pressure and relative humidity 65%.
*2: The applicable compressor is based on the discharge rate and discharge temperature (70°C) of a screw-type compressor.
*3: Accessories should be mounted by the user.
(Unit: mm)
Dimensions: HAA7
(Unit: mm)
HAA15-22 dimensions
(Unit: mm)
HAA37 dimensions
(Unit: mm)
Model | Piping connection port diameter | A | B | C | D | E | F | G | H | J | K | L | M | N | P | Q | R | S |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
HAA15 | 1B union | 460 | 394 | 33 | 70 | 59 | 485 | 428 | 320 | 150 | 150 | 320 | 70 | 58 | 200 | 480 | 220 | 225 |
HAA22 | 1 1/2B union | 588 | 484 | 52 | 70 | 60 | 580 | 505 | 333 | 150 | 150 | 400 | 94 | 65 | 200 | 610 | 220 | 238 |
The outlet air temperature can be calculated by the inlet air temperature, ambient temperature and air flow capacity using the following procedure.
(Example) Inlet air temperature: 100°C, Ambient temperature: 20°C, Air flow capacity: 2,000 L/min (ANR), Air pressure:
0.7 MPa, Model: HAA22-14
Correction factor by ambient temperature
Model | Correction factor line | Air flow (L/min [ANR]) | Inlet air temperature | ||
---|---|---|---|---|---|
50°C | 70°C | 100°C | |||
HAA7 | (A) | 500 | 34.5 | 35 | 35.5 |
(B) | 1,000 | 38 | 40 | 42.5 | |
(C) | 1,500 | 40 | 44 | 47.5 | |
HAA15 | (A) | 1,000 | 33 | 35.5 | 36 |
(B) | 2,200 | 36.5 | 40 | 42.5 | |
(C) | 3,000 | 38 | 42 | 44 | |
HAA22 | (A) | 2,000 | 34 | 37 | 38.5 |
(B) | 3,300 | 36 | 40 | 42.5 | |
(C) | 4,000 | 37 | 41.5 | 45 | |
HAA37 | (A) | 4,000 | 34 | 38 | 39 |
(B) | 5,700 | 35 | 40 | 43 | |
(C) | 7,000 | 36 | 42 | 45 |
Conditions:
Caution
Caution
If the aftercooler is equipped with an auto drain, the following mounting frame is necessary. Mounting frame (Option: Refer to p. 11 Accessories)
Caution
Part Number |
---|
HAA7-062D-T |
Part Number | Price | Name | Minimum Order Qty. | Volume Discount | Days to Ship | Air compressor size (screw type) (KW) | Piping connection port diameter | Power supply voltage (V) | Auto drain | Filter for dust intrusion prevention | Frame | Terminal |
---|---|---|---|---|---|---|---|---|---|---|---|---|
฿ 28,367.20 | SMC COMP RELATED ITEM | 1 Piece(s) | 55 Day(s) | 7.5 | Rp3/4 | Single-phase 200 | With auto drain | None | None | With terminal |
Loading...
Type | After Cooler |
---|
Please check the type/dimensions/specifications of the part HAA7-062D-T in the Air Cooled Aftercooler HAA Series series.
Part Number |
---|
HAA15-101DF |
HAA15-101DFS |
HAA15-101DFS-T |
HAA7-062DF |
HAA7-062DF-T |
HAA7-062DFS |
Part Number | Price | Minimum Order Qty | Volume Discount | Days to Ship | Air compressor size (screw type) (KW) | Piping connection port diameter | Power supply voltage (V) | Auto drain | Filter for dust intrusion prevention | Frame | Terminal |
---|---|---|---|---|---|---|---|---|---|---|---|
฿ 43,842.40 | 1 Piece(s) | 55 Day(s) | 15 | 1B | Single-phase 100 | With auto drain | With dust-protecting filter | None | None | ||
฿ 47,532.00 | 1 Piece(s) | 55 Day(s) | 15 | 1B | Single-phase 100 | With auto drain | With dust-protecting filter | With mounting frame | None | ||
฿ 48,985.60 | 1 Piece(s) | 55 Day(s) | 15 | 1B | Single-phase 100 | With auto drain | With dust-protecting filter | With mounting frame | With terminal | ||
฿ 29,344.00 | 1 Piece(s) | 55 Day(s) | 7.5 | Rp3/4 | Single-phase 200 | With auto drain | With dust-protecting filter | None | None | ||
฿ 30,797.60 | 1 Piece(s) | 55 Day(s) | 7.5 | Rp3/4 | Single-phase 200 | With auto drain | With dust-protecting filter | None | With terminal | ||
฿ 33,033.60 | 1 Piece(s) | 55 Day(s) | 7.5 | Rp3/4 | Single-phase 200 | With auto drain | With dust-protecting filter | With mounting frame | None |