Thermac S Electronic Temperature Controller [E5CS]

Caution
Product Description
· Easily set with DIP switch
· Two alarm types ave been added to the series. Ideal for alarm applications
· Multi-input (thermocouple / platinum temperature-sensing resistance) types are also available
· Easy-to-read digital display with character height of 13.5 mm
Dimensional Drawing of OMRON Temperature Controllers
![THERMAC S Electronic Temperature Controller [E5CS] Outline drawing](http://content.misumi-ec.com/image/upload/t_msmwm_wyg/v1/p/jp/product/wysiwyg/221005345541/221005345541_001_20230801115855.jpg)
* The external dimensions are the same for both models with and without alarm.
Temperature Controllers Layout
![THERMAC S Electronic Temperature Controller [E5CS] Alarm-free type outline drawing](http://content.misumi-ec.com/image/upload/t_msmwm_wyg/v1/p/jp/product/wysiwyg/221005345541/221005345541_002_20230801115855.jpg)
No alarm type
![THERMAC S Electronic Temperature Controller [E5CS] Alarm Type Outline Drawing](http://content.misumi-ec.com/image/upload/t_msmwm_wyg/v1/p/jp/product/wysiwyg/221005345541/221005345541_003_20230801115855.jpg)
Alarm type
Specification Table of OMRON Temperature Controllers
| Power supply voltage | AC100~240V 50/60Hz AC24V 50/60Hz/DC24V | |
|---|---|---|
| Allowable voltage fluctuation range | 85 to 110% of power supply voltage | |
| Power Consumption | 5VA (AC100~240V) 3VA (AC24V)/2W (DC24V) | |
| Temperature Controllers input | Thermocouple types: K, J, L Platinum resistance thermometer types: Pt100, JPt100 Thermistor type: E52-THE Thermocouple/Platinum resistance thermometer multi-input type : K, J, L, T, U, N, R, Pt100, JPt100 | |
| Temperature Controllers Output | Relay Output | AC250V 3A (resistive load) 1c |
| Voltage output (for driving SSR) | DC12V 21mA (with short circuit protection circuit) | |
| Temperature Controllers Method | ON/OFF, 2-degree-of-freedom PID (with automatic PID parameter setting function) | |
| Alarm Output | AC250V 1A (resistive load) 1a | |
| Setting method | Digital setting by front keys | |
| Instruction method | 7-segment digital display (character height 13.5 mm) and deviation indication | |
| Other features | · Prohibits setting changes (key protect) · Input correction · Display unit switching (℃/°F) · Forward/reverse operation switching · Temperature Controllers range, sensor switching (K/J/L, Pt100/JPt100), thermocouple/platinum resistance thermometer multi-input type switches between thermocouple and platinum resistance thermometer · Control cycle switching · 8 mode alarm output · Sensor abnormality detection (excluding thermistor type) | |
| Ambient Temperature Controllers | -10 to +55°C (but no freezing or condensation) / 3-year warranty: -10 to +50°C | |
| Ambient humidity | Relative humidity 25-85% | |
| Storage Temperature Controllers | -25 to +65°C (but no freezing or condensation) | |
Note: Do not use the inverter output as a power supply.
Temperature Controllers Performance
| Indication accuracy (ambient temperature 23℃) | Thermocouple: *1 (±1% of indicated value or ±2°C, whichever is greater) ±1 digit or less Platinum resistance thermometer: *2 (±0.5% of indicated value or ±1°C, whichever is greater) ±1 digit or less Thermistor: *3 (1%FS) ±1 digit or less | |
|---|---|---|
| Temperature Controllers effects | Thermocouple (R): (±2% PV or ±10°C, whichever is greater) ±1 digit or less Other thermocouple: (±2% PV or ±4°C, whichever is greater) ±1 digit or less Platinum resistance thermometer: (±1% PV or ±2°C, whichever is greater) ±1 digit or less Thermistor: (±2% FS) ±1 digit or less | |
| Voltage Effects | ||
| Effects of electromagnetic interference (according to EN61326-1) | ||
| Adjustment sensitivity (at ON/OFF control) | 0.2%FS (0.1%FS for thermocouple/platinum resistance thermometer multi-input type) | |
| Proportional Band | 1 to 999°C (self-tuning, automatically set by auto-tuning) | |
| Integration Time | 1 to 1999s (automatically set by self-tuning and auto-tuning) | |
| Differential Time | 1 to 1999s (automatically set by self-tuning and auto-tuning) | |
| Alarm output setting range | Absolute value alarm: Same as control setting range Others: 0 to full scale input setting range [unit: °C or °F] Alarm hysteresis: 0.2 °C or °F (fixed) | |
| Temperature Controllers Period | 2/20s | |
| Sampling Period | 500ms | |
| Insulation resistance | 20MΩ or more (at DC500V megger) | |
| Withstand voltage | AC2,000V 50/60Hz 1min (between terminals of different polarity live parts) | |
| Vibration resistance | malfunction | 10~55Hz 20m/s2 10min each in X, Y, and Z directions |
| Durability | 10~55Hz 0.75mm 2h each in X, Y, and Z directions | |
| Shock Resistant | malfunction | 100m/s26 directions 3 times each |
| Durability | 300m/s26 directions 3 times each | |
| lifespan | Electrical | Over 100,000 times (relay output type) |
| mass | Approx. 110g (body only) | |
| Protective structure | Front IP50, Enclosure Category 2 (according to IEC60529), Rear case IP20, Terminal IP00 | |
| Memory Protection | Non-volatile memory (number of writes: 1 million times) | |
| EMC | Radiated interference field strength EN55011 Group1 Class ANoise terminal voltage EN55011 Group1 Class AElectrostatic discharge immunity EN61000-4-2 : 4kV contact discharge (Level 2), 8kV air discharge (Level 3) Field strength immunity EN61000-4-3 : 10V/m (80 to 1,000MHz, 1.4 to 2.0GHz amplitude modulated)(Level 3), 10V/m (900MHz pulse modulated) Conducted interference immunity EN61000-4-6 : 3V (0.15 to 80MHz) (Level 2) First transient EN61000-4-4Burst noise immunity: 2kV power line (Level 3), 1kVinput/output signal line (Level 3) Surge immunity EN61000-4-5 : Power line normal mode 1kV common mode 2kV output line (relay output) normal mode 1kV common mode 2kV voltage dip/interruption immunity EN61000-4-11 :0.5 period, 100% (rated voltage) | |
| Certification Standards | UL61010-1 (listing compatible) CSA C22.2 No.1010-1 | |
| Compliance standards | EN61326-1, EN61010-1, IEC61010-1 | |
- U and L: ±2°C ±1 digit or less.
- R at 200°C or less: ±3°C ±1 digit or less.
*2. For platinum resistance thermometers, the following exceptions apply:
- Input setting value 1 of the E5CS-U is 1%FS ±1 digit or less.
*3. For thermistors, the following exceptions apply:
- When set in °C units, accuracy is not guaranteed for temperature indication ranges that exceed ±10%FS of the set Temperature Controllers range.
- When set in °F units, accuracy is not guaranteed for input setting numbers 4 and 9 (609 to 630°F) and for Temperature Controllers indication ranges that exceed -5%FS to +10%FS of the set temperature range.