NCS Conduit Plug (Screw)

Brand :
MISUMI

Caution

    Product Description

    [Features]This is a threaded conduit plug manufactured by Nanaboshi Electric Mfg. Used by attaching to a conduit (cable protective sleeve).


    ● A connector for mounting on conduits (cable protection tube).


    ·The mating counterparts follow. For combination, be sure to combine the male (pin) and female (socket) components.
    Relay Adapters
    Panel Mount Receptacles
    ·To protect the insulator of products of 80A or more from the heat of the solder, the contact can be removed from the insulator.
    · Does not support key position changes.

    Specifications

    NCS Conduit Plug (Screw):Related Image

    ModelShell SizeNumber of CoresShape SymbolContact ShapeWeight
    (g)
    NCS252GP1-2Female
    (Socket)
    63
    363
    468
    569
    668
    769
    867
    252GPM1-2Male
    (Pin)
    62
    362
    463
    564
    667
    764

    ModelShell SizeNumber of CoresShape SymbolContact ShapeWeight
    (g)
    NCS302GP1-2Female
    (Socket)
    85
    385
    485
    585
    685
    785
    890
    1388
    302GPM1-2Male
    (Pin)
    80
    385
    485
    590
    684
    888
    402GP1Female
    (Socket)
    155
    3165
    4170
    5170
    6175
    8175
    10165
    12170
    16170
    20175
    442GPM1Male
    (Pin)
    240
    3240
    4250
    5250
    6250
    8260
    10240
    12240
    16245
    20245
    502GP1Female
    (Socket)
    430
    3445
    4400
    8395
    10400
    15381
    25400
    542GPM1Male
    (Pin)
    505
    3535
    4475
    8465
    10470
    15470
    25465
    602GP1.25Female
    (Socket)
    710
    3740
    4735
    10675
    15665
    30680
    32670
    40685
    6010GPM1.25PMale
    (Pin)
    580
    15545
    30550
    32555
    642GPM1.25880
    3930
    4910

    General-purpose Large Metal Connector (NCS)

    Features

    ● NCS series connectors are round metal connectors that have been used conventionally as general-purpose type connectors.
    ● The structure is simple, robust, mechanically and electrically stable; some items have acquired the mark (Electrical Appliance and Material Safety Act compliant), so they can be used widely from power supply to signal transmission.
    ● There are 10 shell sizes, each of which offers a selection among panel mounting, cable mounting, and relay mounting, providing a wide variety of combinations to suit the application.
    ● Because these connectors are all connected by soldering, no dedicated tool is required for wiring.
    ● The structure is an original design and cannot be coupled with other companies' products.

    Common Specifications

    Material / Finish

    Item Materials Finish
    Shell / Dustproof Cap Zinc Alloy or Brass Chrome Plated or special chemical processing
    Insulator Epoxy Resin
    Contact Copper Alloy Nickel-plated (Shell Size 14 ~ 30)
    Silver-plated (Shell Size 40 ~ 60)
    Gold-plated (Shell Size 30, 13-core)

    Combination Method

    Combination Method

    Characteristics

    Item Characteristics
    Rated Voltage, Current Check with the table below.
    Limit Operating Voltage Check with the table below. Shows the limit voltage value for continuous use of the NCS connector.
    Withstand Voltage No abnormality such as short circuiting occurs when regulated voltage (see table below) is applied for 1 minute between immediately adjacent conductors.
    Insulation Resistance Check with the table below. Resistance value when measured between immediately adjacent conductors with specified voltage.
    Contact Resistance Check with the table below. Conductor resistance value when a pair of contacts are connected at up to the regulation length
    Humidity Resistance No functional defect was found during the JIS-C-8306 humidity test, and the insulation resistance is 10 mΩ or higher.
    Heat Resistance Test No functional defect was found during the JIS-C-8306 heat resistance test.
    Temperature Rise Under correct operating conditions, the temperature rise in conducting parts is 40°C or less when rated current is flowing.
    Corrosion Resistance No functional defect was found during the JIS C 5028 salt water spray test.
    Allowable Operating Temperature Range -40°C ~ +120°C

    Shell
    Size
    Number of Cores Shape Symbol Rated Current
    (A or less)
    Rated Voltage
    (V or less)
    Limit Operating Voltage (Note) Withstand Voltage (VAC) Insulation Resistance
    (MΩ or higher)
    Contact Resistance
    (mΩ or less)
    Applicable Electric Wire Size
    Conductor Cross-sectional Area mm2 Parentheses show AWG
    Applicable Electric Wire Finished Outer Diameter (mm)
    14 1.2 P, R, AD 5 125 200 1,000 2,000 3 0.75 (18) φ5.5 ~ 7.0
    16 1 P, R
    AD
    10 125 200 1,000 2,000 3 1.25 (18) φ6.5 ~ 8.0
    2.3.4 5 0.75 (18)
    16 2.3 PM, RF, ADF 5 125 200 1,000 2,000 3 0.75 (18) φ6.5 ~ 8.0
    25 2.3.4 P, R, AD
    GP1-2, LP
    10 250 400 2,000 2,000 3 2 (14) φ9.5 ~ 11.5
    5 1,800
    6.7 300
    8 5 1.25 (16)
    25 2.3.4 PM, RF, ADF
    GPM1-2
    10 250 400 2,000 2,000 3 2 (14) φ9.5 ~ 11.5
    5 1,800 1.25 (16)
    6.7 5 300
    30 2 P, R, AD
    GP1-2
    15 250 400 2,000 2,000 3 3.5 (12) φ11.0 ~ 13.0
    3.4 2 (14)
    5.6.7 1,800
    8 10 300
    13 5 - 1,500 1.25 (16)
    30 2.3.4 PM, RF, ADF
    GPM1-2
    15 250 400 2,000 2,000 3 2 (14) φ11.0 ~ 13.0
    5 1,800
    6 10 -
    8 5 300 1.25 (16)
    40 2.3.4 PM, RF, ADF
    GP1
    30 250 500 2,500 2,000 3 5.5 (10) φ15.0 ~ 17.0
    5.6.8 20 400 2,000
    10 3-piece - 10, 7-piece - 5 300 1,800 Contact No. 1, 9, 10-2 (14) , Others - 1.25 (16)
    12 3-piece - 10, 9-piece - 5 Contact No. 1, 9, 10-2 (14) , Others - 1.25 (16)
    16 3-piece - 10, 13-piece - 5 Contact No. 1, 14, 15-2 (14) , Others - 1.25 (16)
    20 5 1.25 (16)
    44 2.3.4 PM, RF, ADF
    GPM1
    30 250 500 2,500 2,000 3 5.5 (10) φ15.0 ~ 19.0
    5.6.8 20 400 2,000
    10 3-piece - 10, 7-piece - 5 300 1,800 Contact No. 1, 9, 10-2 (14) , Others - 1.25 (16)
    12 3-piece - 10, 9-piece - 5 Contact No. 1, 9, 10-2 (14) , Others - 1.25 (16)
    16 3-piece - 10, 13-piece - 5 Contact No. 1, 14, 15-2 (14) , Others - 1.25 (16)
    20 5 1.25 (16)
    50 2.3 P, R, AD
    GP1
    80 500 600 3,000 5,000 1 30 (2) φ19.0 ~ 23.0
    4 50 250 500 2,500 2,000 3 14 (6)
    8 25 400 2,000 3.5 (12)
    10 20 300
    15 15
    25 4-piece - 15, 21-piece - 5 1,800 Contact No. 3, 6, 19, 22-3.5 (12), Others - 2 (14)
    54 2.3 PM, RF, ADF
    GPM1
    80 500 600 3,000 5,000 1 30 (2) φ19.0 ~ 26.0
    4 50 250 500 2,500 2,000 3 14 (6)
    8 25 400 2,000 3.5 (12)
    10 20 300
    15 15
    25 4-piece - 15, 21-piece - 5 1,800 Contact No. 3, 6, 19, 22-3.5 (12), Others - 2 (14)
    60 2 P, R, AD
    GP1.25
    150 500 600 3,000 5,000 1 50 (0) φ29.0 ~ 33.0
    3
    4 80 30 (2)
    10 30 250 300 2,500 2,000 3 8 (8)
    15 15 3.5 (12)
    30, 40 5 1,500 2 (14)
    32 3-piece - 15, 29-piece - 5 Contact No. 2, 24, 28-3.5 (12), Others - 2 (14)
    60 10 PM, RF, ADF
    GPM1.25
    30 250 300 2,000 2,000 3 8 (8) φ29.0 ~ 33.0
    15 15 3.5 (12)
    30 5 1,500 2 (14)
    32 3-piece - 15, 29-piece - 5 1,800 Contact No. 2, 24, 28-3.5 (12), Others - 2 (14)
    64 2 PM, RF, ADF
    GPM1.25
    150 500 600 3,000 5,000 1 50 (0) φ31.0 ~ 36.0
    3
    4 80 30 (2)
    (Note): Shows the limit voltage value for continuous use of the NCS connector. Follow the rated voltage if there is no indication on the connector.

    NCS Connector Contact Arrangement Diagram

    NCS Connector Contact Arrangement Diagram

    NCS Connector Contact Arrangement Diagram

    Connection Work Method

    1. Disassemble the connector according to the following.
    Connector
    Note: If a contact for 80 A or 150 A is mounted, use the following procedure.

    (1) Loosen the lock screws and remove the insulator from the connector body (turn counterclockwise)
    (2) Loosen the clamp screws and remove the clamp saddle from the connector body
    Contact Wrench
    (1) Insert the contact wrench from the coupling side and remove the contact locking nut
    2. Pass the disassembled parts through the cable in the order shown below.

    Note: Avoid mistakes in the order or direction of parts.
    Parts
    3. Following the figure and table below, perform preparatory soldering for the core wires of the end-processed cable.

    Cable End Processing Dimensional Drawing
    4. Solder

    With Solder (1) Insert the core wire with extra solder into the contact solder pot
    (2) Heat the contact and the core wire with a soldering iron (conductor cross-sectional area 0.75 ~ 3.5 mm2 (AWG18 ~ AWG12) 30 seconds or less, and conductor cross-sectional area 5.5 ~ 14 mm2 (AWG10 ~ AWG6) 60 seconds or less)
    (3) Apply solder and fill the gap between the contact and the core wires

    5. Assemble the connector according to the following.

    Connector (1) Screw the insulator firmly to the connector body (contacts for 80 A and 150 A should be installed with a contact wrench beforehand)
    (2) Tighten the lock screws (tighten the connector body and insulator to the extent that they do not loosen when rotated by hand)
    (3) Tighten the clamp screw and attach the clamp saddle to the plug body

    Conductor Area and Soldering Iron

    Soldering Iron
    Wattage
    Iron Tip
    Temperature (°C)
    Wire Size (Upper Part mm2, Lower Part AWG)
    0.75 1,25 2 3.5 5.5 8 14
    18 16 14 12 10 8 6
    15 W 320
    ~
    370
    30 W
    60 W
    80 W
    100 W
    150 W
    200 W

    Cable End Processing Dimensional Table

    Shape Symbols for P and AD (LP, GP * Common)
    · Shape symbols LP, GP * are the same as P.
    · Shape symbol R is the same as AD, but can be used with A dimension at the length of your choice.
    Product No. Terminal Number A B Product No. Terminal Number A B Product No. Terminal Number A B Product No. Terminal Number A B
    NCS-14-1-P All Poles 13.5 6 NCS-40-5-P All Poles 23 10 NCS-14-1-AD All Poles 20 6 NCS-40-5-AD All Poles 35 10
    NCS-14-2-P 1
    2
    11
    10
    3.5
    4
    NCS-40-6-P 6
    Other Poles
    22
    23
    NCS-14-2-AD NCS-40-6-AD
    NCS-16-1-P All Poles 13 6 NCS-40-8-P 8 Other Poles 22
    23
    NCS-16-1-AD 11 NCS-40-8-AD
    NCS-16-2-P 1
    2
    13
    11
    4 NCS-40-10-P 1.9.10
    Other Poles
    22
    23
    7 NCS-16-2-AD 20 NCS-40-10-AD 1.9.10
    Other Poles
    34
    35
    7
    NCS-16-3-P 1
    2.3
    11
    13
    NCS-40-12-P NCS-16-3-AD NCS-40-12-AD
    NCS-16-4-P 1.2.4
    3
    11
    10
    NCS-40-16-P 1.14.15
    Other Poles
    22
    23
    NCS-16-4-AD NCS-40-16-AD 1.14.15
    Other Poles
    34
    35
    NCS-25-2-P All Poles 18 8 NCS-40-20-P 1.6.9
    Other Poles
    22
    23
    NCS-25-2-AD 24 7 NCS-40-20-AD All Poles 35
    NCS-25-3-P NCS-50-2-P All Poles 35 13 NCS-25-3-AD NCS-50-2-AD 42 13
    NCS-25-4-P NCS-50-3-P NCS-25-4-AD NCS-50-3-AD
    NCS-25-5-P 17 7 NCS-50-4-P 33 11 NCS-25-5-AD NCS-50-4-AD 40 11
    NCS-25-6-P 6
    Other Poles
    13
    17
    NCS-50-8-P 8
    Other Poles
    32
    34
    7 NCS-25-6-AD NCS-50-8-AD 7
    NCS-25-7-P 7
    Other Poles
    13
    17
    NCS-50-10-P 10
    Other Poles
    32
    36
    NCS-25-7-AD NCS-50-10-AD
    NCS-25-8-P 8
    Other Poles
    13
    17
    NCS-50-15-P All Poles 34 9 NCS-25-8-AD NCS-50-15-AD 42 9
    NCS-30-2-P All Poles 19 8 NCS-50-25-P 3.6.19.22
    Other Poles
    30
    34
    9
    8
    NCS-30-2-AD 24 8 NCS-50-25-AD 3.6.19.22
    Other Poles
    42
    43
    9
    8
    NCS-30-3-P 7 NCS-60-2-P All Poles 43 15 NCS-30-3-AD 7.5 NCS-60-2-AD All Poles 45 15
    NCS-30-4-P NCS-60-3-P NCS-30-4-AD NCS-60-3-AD
    NCS-30-5-P NCS-60-4-P 13 NCS-30-5-AD NCS-60-4-AD 13
    NCS-30-6-P 6
    Other Poles
    16
    19
    NCS-60-10-P 41 12 NCS-30-6-AD NCS-60-10-AD 47 12
    NCS-30-7-P 7
    Other Poles
    16
    19
    NCS-60-15-P 9 NCS-30-7-AD NCS-60-15-AD 9
    NCS-30-7H-P All Poles 19 NCS-60-30-P 43 8 NCS-30-7H-AD 7 NCS-60-30-AD 48 8
    NCS-30-8-P 8
    Other Poles
    16
    19
    NCS-60-32-P 2.24.28
    Other Poles
    39
    43
    9
    8
    NCS-30-8-AD NCS-60-32-AD 2.24.28
    Other Poles
    47
    48
    9
    8
    NCS-30-13-P All Poles 17 6 NCS-60-40-P All Poles 43 8 NCS-30-13-AD 6 NCS-60-40-AD All Poles 48 8
    NCS-40-2-P 22 10 NCS-40-2-AD 35 6
    NCS-40-3-P NCS-40-3-AD
    NCS-40-4-P NCS-40-4-AD
    Shape Symbols for P and AD (LP, GP * Common)
    · Shape symbols LP, GP * are the same as P.
    · Shape symbol R is the same as AD, but can be used with A dimension at the length of your choice.
    Product No. Terminal Number A B Product No. Terminal Number A B Product No. Terminal Number A B Product No. Terminal Number A B
    NCS-16-2-PM All Poles 13 6 NCS-44-16-PM 1.14.15
    Other Poles
    25
    26
    7 NCS-16-2-ADF All Poles 20 6 NCS-44-16-ADF 1.14.15
    Other Poles
    31
    32
    7
    NCS-16-3-PM NCS-44-20-PM All Poles 26 NCS-16-3-ADF NCS-44-20-ADF 1.6.9
    Other Poles
    31
    32
    NCS-25-2-PM 18 7 NCS-54-2-PM 45 13 NCS-25-2-ADF 24 8 NCS-54-2-ADF All Poles 50 13
    NCS-25-3-PM NCS-54-3-PM NCS-25-3-ADF 7 NCS-54-3-ADF
    NCS-25-4-PM NCS-54-4-PM 43 11 NCS-25-4-ADF NCS-54-4-ADF 46 11
    NCS-25-5-PM 6 NCS-54-8-PM 7 NCS-25-5-ADF 6 NCS-54-8-ADF 8 Other Poles 45 47 7
    NCS-25-6-PM NCS-54-10-PM NCS-25-6-ADF NCS-54-10-ADF 10
    Other Poles
    45
    47
    NCS-25-7-PM NCS-54-15-PM 45 9 NCS-25-7-ADF NCS-54-15-ADF All Poles 47 9
    NCS-30-2-PM 22 8 NCS-54-25-PM 3.6.19.22
    Other Poles
    45
    48
    9
    8
    NCS-30-2-ADF 26 8 NCS-54-25-ADF 3.6.19.22
    Other Poles
    31
    35
    9
    8
    NCS-30-3-PM NCS-60-10-PM All Poles 46 12 NCS-30-3-ADF 7 NCS-60-10-ADF All Poles 41 12
    NCS-30-4-PM NCS-60-15-PM 9 NCS-30-4-ADF NCS-60-10-ADF 9
    NCS-30-5-PM 21 NCS-60-30-PM 47
    46
    8 NCS-30-5-ADF NCS-60-30-ADF 43 8
    NCS-30-6-PM 20 7 NCS-60-32-PM 2.24.28
    Other Poles
    47 9
    8
    NCS-30-6-ADF NCS-60-32-ADF 2.24.28
    Other Poles
    39
    43
    9
    8
    NCS-30-8-PM NCS-64-2-PM All Poles 47 15 NCS-30-8-ADF NCS-64-2-ADF All Poles 47 15
    NCS-44-2-PM 26 10 NCS-64-3-PM NCS-44-2-ADF 31 10 NCS-64-3-ADF
    NCS-44-3-PM NCS-64-4-PM 13 NCS-44-3-ADF NCS-64-4-ADF 13
    NCS-44-4-PM NCS-44-4-ADF
    NCS-44-5-PM NCS-44-5-ADF 32
    NCS-44-6-PM NCS-44-6-ADF 6
    Other Poles
    31
    32
    NCS-44-8-PM NCS-44-8-ADF 8
    Other Poles
    31
    32
    NCS-44-10-PM 1.9.10
    All Poles
    25
    26
    7 NCS-44-10-ADF 1.9.10
    Other Poles
    31
    32
    7
    NCS-44-12-PM NCS-44-12-ADF
    Viewed Products
    Recently Viewed Products
    My Components
    My Components
    0
    Cart
    Cart
    Economy Series
    MRO Product

    Chat with MISUMI

    Chat service is available for any inquiry to MISUMI

    Service hours

    9:00 - 18:00 (Mon-Sat)

    For out of service hours, you can leave a message to us.
    We will reply to your inquiries on the next business day.
    (except Sundays and public holidays).

    Noted for use

    Chat service is for Corporate customers and limited for Thai language.

    Request for Quotation and Place Order is not available on Chat.

    Start chat