[Applications]A measure to prevent noise intrusion from 3-phase power supply lines [Features] · Improved workability with self-lifting screws and opening/closing covers · DIN rail mount type also available
Model | Circuit Configuration | Rated Current | Shape (Mounting Method) |
ENF-RTEN-5006 | 3-Phase | 6A | Standard (Direct Mount) |
ENF-RTEN-5006D | DIN Rail Mountable | ||
ENF-RTEN-5010 | 10A | Standard (Direct Mount) | |
ENF-RTEN-5010D | DIN Rail Mountable | ||
ENF-RTEN-5020 | 20A | Standard (Direct Mount) | |
ENF-RTEN-5020D | DIN Rail Mountable | ||
ENF-RTEN-5030 | 30A | Standard (Direct Mount) | |
ENF-RTEN-5030D | DIN Rail Mountable | ||
ENF-RTEN-5050 | 50A | Standard (Direct Mount) |
Model | Standard | ENF-RTEN-5006 | ENF-RTEN-5010 | ENF-RTEN-5020 | ENF-RTEN-5030 | ENF-RTEN-5050 |
DIN Rail Mountable | ENF-RTEN-5006D | ENF-RTEN-5010D | ENF-RTEN-5020D | ENF-RTEN-5030D | - | |
Manufacturer Part Number | Standard | RTEN-5006 | RTEN-5010 | RTEN-5020 | RTEN-5030 | RTEN-5050 |
DIN Rail Mountable | RTEN-5006D | RTEN-5010D | RTEN-5020D | RTEN-5030D | - | |
Circuit Configuration | 3-Phase | |||||
Rated Voltage (AC / DC) | 500V | |||||
Rated Current (AC / DC) | 6A | 10A | 20A | 30A | 50A | |
Withstand Voltage | 2,500 VAC / 1 Minute Interval at 20°C and 65% RH: Between Line-Earth | |||||
Insulation Resistance | 100 MΩ min. 500 VDC at 20°C, 65% RH: Between Line-Earth | |||||
Leakage Current | 2.5 mA max. (250 V) / 5.0 mA max. (500 V) | |||||
Direct Current Resistance | 145 mΩ max. | 60 mΩ max. | 25 mΩ max. | 13 mΩ max. | 7 mΩ max. | |
Attenuation Volume Guarantee Range 25 dB Guarantee | Common Mode | 0.2 ~ 10MHz | 0.3 ~ 8MHz | 0.5 ~ 8MHz | 0.3 ~ 7MHz | 0.5 ~ 7MHz |
Differential Mode | 0.2 ~ 30MHz | 0.2 ~ 30MHz | 0.2 ~ 30MHz | 0.2 ~ 30MHz | 0.2 ~ 30MHz | |
Operation Environment | Temperature: -25 ~ +85 °C, 15 ~ 85% RH (No Condensation) | |||||
Safety Standards | UL1283, EN60939 | |||||
Mass | Standard | 360g | 360g | 560g | 560g | 1100g |
DIN Rail Mountable | 400g | 400g | 620g | 620g | - |
Circuit Configuration | Three-phase | Wiring Method | Screw fastening | Representative Standard | UL |
---|