• มิซูมิแจ้งวันหยุดทำการในเดือนตุลาคม 2562 คลิก | MISUMI's Holiday in October 2019 click

CC-Link IE Field Ethernet Adapter Unit

CC-Link IE Field Ethernet Adapter Unit

General-purpose sequencer that is capable of reading data from devices.
[Features]
· Unit to connect the external device connected to the Ethernet to the CC-Link IE field network.
[Applications]
· Ideal for use in network communication.

(i)Caution

  • This product belongs in RoHS Directive under Category 9 "Monitoring and control equipment" with exclusion from the usage restriction of phthalate esters until 21 July 2021.

CC-Link IE Field Network Ethernet Adapter Unit Specifications

CC-Link IE Field Ethernet Adapter Unit: related image

NZ2GF-ETB external appearance

CC-Link IE Field Ethernet Adapter Unit: related image

NZ2GF-ETB outline drawing (unit: mm)

  • Approved standards: UL/cUL, CE (EMC), KC
  • Type of unit: Ethernet adapter

Performance Specifications

CC-Link IE Field Network Specifications-
Maximum Link Points Per NetworkRWw8,192 points, 16 KB
RWr8,192 points, 16 KB
RX16,384 points, 2 KB
RY16,384 points, 2 KB
Maximum Link Points Per StationRWw1,024 points, 2 KB
RWr1,024 points, 2 KB
RX2,048 points, 256 bytes
RY2,048 points, 256 bytes
Station Number1 to 120
Network No.1 to 239
Communication MethodToken passing method
Communication Speed1 Gbps
Transmission Path TypeLine type, star type (Line type and star type can be combined.), ring type
Communication CableEthernet cable meeting the 1000BASE-T standard: Category 5e or higher (with double shields / STP), straight cable
Maximum Distance Between StationsMaximum 100 m (complies with ANSI / TIA / EIA-568-B (Category 5e).)
Total Extension Distance Per NetworkLine connection: 12,000 m (when 121 units are connected)
Star connection: Varies depending on the system.
Ring connection: 12,100 m (when 121 units are connected)
Number Of Cascade Connection LevelsUp to 20 levels
Ethernet Specification-
EthernetNumber Of ConnectionsFor User32
To Be Opened Automatically1
For MELSOFT Connection3 (1 for TCP connection, 1 for UDP connection, 1 for direct connection)
Port Number Of Own Station1,025 to 4,999, 5,011 to 65,534 (0401H to 1387H, 1393H to FFFEH)
Number Of Simultaneously Connected UnitsUp to 32 units
Communication Speed1 Gbps / 100 Mbps
Communication ModeFull Duplex / Half Duplex
Transmission MethodBase Band
Communication CableBased On 1 Gbps CommunicationEthernet cable meeting the 1000BASE-T standard (Category 5e or higher, RJ-45 with double shield)
Based On 100 Mbps CommunicationEthernet cable meeting the 100BASE-TX standard (Category 5e or higher, RJ-45 with double shield)
Maximum Distance Between Switching Hub And NodeMax. 100 m
Number Of Cascade Connection LevelsUp to 20 levels
Unit Specification-
Number Of DevicesInput [X]8,192 points (X0 to X1FFF are assigned to RX0 to RX1FFF)
Output [Y]8,192 points (Y0 to Y1FFF are assigned to RY0 to RY1FFF)
Link Register [W]8,192 points (1,024 points from W0 to W3FF are assigned to RWw0 to RWw3FF. 1,024 points from W1000 to W13FF are assigned to RWr0 to RWr3FF.)
Link Special Relay [SB]8,192 points (SB0 to 1FFF)
Link Special Register [SW]8,192 points (SW0 to 1FFF)
Special Relay [SM]2,048 points (SM0 to 2,047) (The number of device points is fixed.)
Special Register [SD]2,048 points (SD0 to 2,047) (The number of device points is fixed.)
Clock FunctionYear, month, day, hour, minute, second (automatic detection of leap year)
Unit Power SupplyVoltage24 V DC (-35 to +30%)
Current0.6 A
Inrush Current100 A, 1 ms or less
Allowable Momentary Power Loss DurationWithin 10 ms
Withstand VoltageBetween all inputs / LG at once and all outputs / FG at once, 510 V AC / 1 minute (altitude 0 to 2,000 m)
Insulation ResistanceBetween all inputs / LG at once and all outputs / FG at once, between all inputs at once and LG, between all outputs at once and FG: 10 MΩ or more at 500 V DC on an insulation resistance meter
Operation IndicationLED indicator (Normal: Green light is lit. Error: Unlit)
FuseBuilt-in (cannot be replaced by the user)
External Wiring Connection MethodScrew Terminal Block (M3.5 Screw)
External DimensionsHeight (H)90 mm
Width (W)135 mm
Depth (D)109 mm
Mass0.70 kg

General Specifications

Ambient Operating Temperature0 to 55℃
Ambient Storage Temperature-25 to 75°C
Ambient Operating Humidity5 to 95% RH, assuming no condensation
Ambient Storage Humidity5 to 95% RH, assuming no condensation
Vibration ResistanceJIS B 3502, IEC 61131-2 compliantUnder Intermittent VibrationFrequency: 5 to 8.4 Hz, single amplitude: 3.5 mm
Frequency: 8.4 to 150 Hz, constant acceleration: 9.8 m/s2
Sweeps: 10 sweeps in each direction of X, Y and Z
Under Continuous VibrationFrequency: 5 to 8.4 Hz, single amplitude: 1.75 mm
Frequency: 8.4 to 150 Hz, constant acceleration: 4.9 m/s2
Impact ResistanceConforms to JIS B 3502, IEC 61131-2 (147 m/s2, 3 sweeps in 3 directions of X, Y and Z)
Operating AtmosphereNo corrosive gas
Operating Altitude0 to 2,000 m
Installation LocationInside the control panel
Overvoltage CategoryII or lower
Pollution Degree2 or less
Equipment ClassClass I
Part Number
NZ2GF-ETB
Part NumberVolume DiscountDays to Shipวันจัดส่งRoHS
Same day 6

Loading...กำลังโหลด …

  1. 1

Basic Informationข้อมูลพื้นฐาน

Representative Standard CE / UL Type of unit Ethernet Adapter Communication Speed(kbps) 1Gbps/100Mbps

Please check the type/dimensions/specifications of the part NZ2GF-ETB in the CC-Link IE Field Ethernet Adapter Unit series.โปรดตรวจสอบ ชนิด / มิติ / รายละเอียด ของชิ้นส่วน NZ2GF-ETB ในชุด CC-Link IE Field Ethernet Adapter Unit

Additional Products in this Category

Customers Who Viewed This Item Also Viewed

Tech Support

Third-party Brand
Tel:038-959200 Press 7 / FAX:038-959288
9:00 - 18:00 (Monday - Friday)