(!) Since support from Microsoft will end on January 14 2020, Windows 7 user might not be able to use MISUMI website effectively. Please consider to update your system as ‘MISUMI Website system requirement’.
Select part number to Order Now/ Add to Cart
Power supply designed to supply power exclusively to CC-Link/LT systems from an external power source.
[Features]
· Power supply for general-purpose sequencer.
· Built-in 2‑A power supply.
· Stable 24 V DC.
[Applications]
· Power supply.
· Exclusively for CC-Link/LT.
CL1PSU-2A external appearance
CL1PSU-2A dimensional drawing, unit: mm
Input | Rated Voltage | 100/120/200/230/240 V AC |
---|---|---|
Allowable Voltage Range | 85 to 264 V AC | |
Rated Current | 1.2 A / 100 V AC, 0.7 A / 200 V AC | |
Rated Frequency | 50/60 Hz | |
Power Supply Fuse | 3.15 A | |
Inrush Current | Max. 50 A / 100 V AC, Max. 60 A / 200 V AC | |
Output | Output Voltage | 24 V DC +10%/-5% |
Output Current | 0.01 to 2 A, Subject to derating depending on the ambient temperature and power supply voltage. [Use the system so that the total current consumption of each station does not exceed 2 A when power is supplied (except immediately after the power is turned on).] | |
Ripple Noise | 500 mVp‑p or less | |
Allowable Momentary Power Outage Duration | PS2: Operation continues after a momentary power outage of 10 ms or less. | |
Protection Grade | IP1X | |
Protection Function | Excess Current Protection | 110 to 160%, drooping characteristics, automatically reset |
Excess Voltage Protection | 27 to 33 V, output cutoff, not automatically reset | |
External Connection Method | · Power supply to dedicated power supply: terminal block, 3 points (M3 screw) · Power supply to communication part and CC-Link/LT system: dedicated CC-Link/LT connector (4 pins) × 2 | |
Mass | 0.4 kg |
Ambient Temperature | 0 to 55°C - When Operating, -25 to 70°C - When Saving | ||
---|---|---|---|
Relative Humidity | 5 to 95% RH (No Condensation) - When Operating / When Saving | ||
Vibration Resistance | Under Intermittent Vibration | Frequency: 10 To 57 Hz | Single amplitude: 0.075 mm 10 times in each direction of X, Y and Z (total 80 minutes each) |
Frequency: 57 To 150 Hz | Acceleration: 9.8 m/s2 10 times in each direction of X, Y and Z (total 80 minutes each) | ||
Under Continuous Vibration | Frequency: 10 To 57 Hz | Single amplitude: 0.035 mm 10 times in each direction of X, Y and Z (total 80 minutes each) | |
Frequency: 57 To 150 Hz | Acceleration: 4.9 m/s2 10 times in each direction of X, Y and Z (total 80 minutes each) | ||
Impact Resistance | 147 m/s2, 3 times in each direction of X, Y and Z | ||
Noise Resistance | Achieved through a noise simulator with a noise voltage of 1,000 Vp‑p, noise width of 1 μs and frequency of 25 to 60 Hz. | ||
Withstand Voltage | AC type: 15,000 V AC for 1 min DC type: 5,000 V AC for 1 min | ||
Insulation Resistance | Between all external terminals at once and the earth terminal: 10 MΩ at 500 V DC on an insulation resistance meter | ||
Operating Atmosphere | There shall be no corrosion gas or flammable gas and not much conductive dust. | ||
Altitude Of Use | 2,000 m or lower Cannot be used in environments pressurized higher than the atmospheric pressure. Doing so may cause failures. | ||
Installation Location | Inside the control panel | ||
Overvoltage Category | II or lower Indicates the assumed wiring part to which the applicable equipment is connected between the public network and the mechanical system in plant. Category II applies to the equipment to which power is supplied from a fixed facility. The surge withstand voltage for equipment of up to 300 V in rating is 2,500 V. | ||
Pollution Degree | 2 or lower Index to indicate the degree of conductive material generation in the use environment. Pollution degree 2 indicates that only non-conductive contaminants will generate. However, temporary conduction may still occur in the environment due to accidental condensation. | ||
Earthing | D-type earthing (earthing resistance: 100 Ω or less) |
Part Number |
---|
CL1PSU-2A |
Part Number | Price | Name | Minimum Order Qty. | Volume Discount | Days to Ship |
---|---|---|---|---|---|
฿ 4,928.00 ฿ 4,224.28 | PLC(EXPANSION UNIT) | 1 Piece(s) | 6 Day(s) |
Loading...
Rated Input Voltage | AC100V / AC120V / AC200V / AC230V / AC240V | Maximum Output Voltage/ Current | DC24V· 2A | Note | CC-Link/LT Dedicated Power Supply (2A) - Compatible Standards: UL/ cUL, CE (EMC), CE (LVD) |
---|
Please check the type/dimensions/specifications of the part CL1PSU-2A in the Dedicated CC-Link/LT Power Supply series.